Home

href="
®
Non-Programmable  
Digital  
FocusPRO  
Thermostat  
5000Series  
Installation  
Instructions  
Wallplate installation  
Remove the wallplate from the thermostat,  
then follow directions below for mounting.  
1
2
. Remove battery holder.  
. Pull here to remove wallplate from new  
thermostat.  
3
4
. Pull wires through wire hole.  
. Position wallplate on wall, level and mark  
hole positions with pencil.  
5
6
. Drill holes at marked positions as shown  
below, then tap in supplied wall anchors.  
. Place wallplate over anchors, insert and  
tighten mounting screws.  
Wire hole  
Mounting  
screws  
Drill 3/16"  
holes for  
drywall.  
Drill 7/32"  
holes for  
plaster.  
href="
Power options  
Keep wires in this  
shaded area  
Remove factory-  
installed jumper  
only for two-  
transformer  
systems.  
Insert batteries for primary  
or backup power.  
M29370  
Connect C for primary AC power  
(
optional if batteries are installed).  
Wiring terminal designations  
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.  
Conventional Terminals: Heat Pump Terminals:  
Rc  
R
24VAC power from cooling  
transformer  
24VAC power from heating  
transformer  
Rc  
R
24VAC power from cooling  
transformer  
24VAC power from heating  
transformer  
W
Heat relay (stage 1)  
O/B Changeover valve  
W2 Heat relay (stage 2)  
Y
Y2  
Compressor contactor  
Compressor contactor (stage 2)  
-TH5320U only  
Y
Compressor contactor (stage 1)  
Compressor contactor (stage 2)  
Fan relay  
Y2  
G
C
G
Fan relay  
24VAC common. For 2 transformer  
systems, use common wire from  
cooling transformer.  
Aux/E Auxiliary/Emergency heat relay  
L
C
Sends output when set to Em. Heat  
24VAC common  
TH5110D  
Rc  
R
TH5110D Rc  
R
Y
Y
C
C
W
G
O/B  
G
TH5220D  
TH5220D  
Y2 W2 G  
W
C
Y
R
Rc  
L
Aux G O/  
C
Y
R
Rc  
B
E
TH5320U  
TH5320U  
Y2 W2 G  
W
C
Y
R
Rc  
L
Y2 Aux G O  
C
Y
R
Rc  
/
B
E
MCR29371A  
2
href="
Wiring conventional systems  
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.  
1
H/1C System  
Heat-only System  
with Fan  
G W C  
Y
R Rc  
G W C  
R Rc  
(
1 transformer)  
Rc  
R
Y
C
W
G
Power [1]  
Rc  
R
C
W
G
Power [1]  
[R+Rc joined by jumper]  
Compressor contactor  
24VAC common [3]  
Heat relay  
[R+Rc joined by jumper]  
24VAC common [3]  
Heat relay  
Fan relay  
Fan relay  
Cool-only System  
Heat-only  
System  
Rc  
R
Y
C
G
Power [1]  
G
C
Y
R Rc  
W C  
R Rc  
[R+Rc joined by jumper]  
Compressor contactor  
24VAC common [3]  
Fan relay  
Rc  
R
C
Power [1]  
[R+Rc joined by jumper]  
24VAC common [3]  
Heat relay  
W
2
H/2C System  
Heat-only  
System  
(1 transformer) [6]  
Y2 W2 G W C  
Y
R Rc  
W C  
Y
R Rc  
Rc  
R
Power [1]  
[R+Rc joined by jumper]  
(
Series 20) [5]  
Rc  
R
Y
[R+Rc joined by jumper]  
Y
C
W
G
Compressor contactor (stage 1)  
24VAC common [3]  
Heat relay (stage 1)  
Fan relay  
Series 20 valve terminal “R” [1]  
Series 20 valve terminal “W”  
24VAC common [3]  
C
W
Series 20 valve terminal “B”  
W2 Heat relay (stage 2)  
Y2 Compressor contactor (stage 2)  
Heat-only  
System  
C
Y
R
Rc  
2H/2C System  
Y2 W2G W C  
Y
R Rc  
(normally open zone valve) [5]  
(2 transformers) [6]  
Rc  
R
Y
[R+Rc joined by jumper]  
Power [1]  
Normally open zone valve  
24VAC common [3]  
Rc  
R
Y
C
W
G
Power (cooling transformer) [1, 2]  
Power (heating transformer) [1, 2]  
Compressor contactor (stage 1)  
24VAC common [3, 4]  
Heat relay (stage 1)  
C
1
H/1C System  
Fan relay  
(
2 transformers)  
G W C  
Y
R
Rc  
W2 Heat relay (stage 2)  
Y2 Compressor contactor (stage 2)  
Rc  
R
Y
C
W
G
Power (cooling transformer) [1, 2]  
Power (heating transformer) [1, 2]  
Compressor contactor  
24VAC common [3, 4]  
Heat relay  
Fan relay  
NOTES  
[6] In Installer Setup, set system type to  
2Heat/2Cool Conventional.  
Wire specifications:  
Use 18- to 22-gauge thermostat wire.  
Shielded cable is not required.  
[7] In Installer Setup, set changeover valve to  
O or B.  
[
1] Power supply. Provide disconnect means  
and overload protection as required.  
[8] In Installer Setup, set system type to  
2Heat/1Cool Heat Pump.  
[
[
[
2] Remove jumper for 2-transformer systems.  
3] Optional 24VAC common connection.  
4] Common connection must come from cool-  
ing transformer.  
5] In Installer Setup, set system type to  
Heat Only.  
[9] In Installer Setup, set system type to  
2
Heat/2Cool Heat Pump.  
[
[
10] In Installer Setup, set system type to  
Heat/2Cool Heat Pump.  
11] L terminal sends a continuous output when  
thermostat is set to Em. Heat. Connect  
to Honeywell zoning panels to switch the  
panel to Emergency Heat.  
3
[
3
href="
Wiring heat pump systems  
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.  
1
H/1C Heat Pump  
2H/2C Heat Pump  
System  
G
C
Y
R Rc  
L Y2  
G
C Y R Rc  
System  
Rc  
R
Y
Power [1]  
(TH5320U only) [9]  
[R+Rc joined by jumper]  
Compressor contactor  
24VAC common [3]  
Rc  
R
Power [1]  
[R+Rc joined by jumper]  
C
Y
C
Compressor contactor (stage 1)  
24VAC common [3]  
O/B Changeover valve [7]  
Fan relay  
G
O/B Changeover valve [7]  
G
Y2  
L
Fan relay  
Compressor contactor (stage 2)  
Sends output when set to Em. Heat [11]  
2
H/1C Heat Pump  
System (TH5220D only) [8] L Aux G  
C
Y
R Rc  
E
Rc  
R
Y
Power [1]  
[R+Rc joined by jumper]  
Compressor contactor  
24VAC common [3]  
3H/2C Heat Pump  
System  
(TH5320U only) [10]  
L Y2AuxG  
E
C Y R Rc  
C
O/B Changeover valve [7]  
Fan relay  
Aux/E Auxiliary/Emergency heat relay  
Rc  
R
Y
Power [1]  
[R+Rc joined by jumper]  
Compressor contactor (stage 1)  
24VAC common [3]  
G
L
Sends output when set to Em. Heat [11]  
C
O/B Changeover valve [7]  
Fan relay  
Aux/E Auxiliary/Emergency heat relay  
2
H/1C Heat Pump  
G
System  
L
AuxG  
E
C Y R Rc  
(
TH5320U only) [8]  
Y2  
L
Compressor contactor (stage 2)  
Sends output when set to Em. Heat [11]  
Rc  
R
Y
Power [1]  
[R+Rc joined by jumper]  
Compressor contactor  
24VAC common [3]  
C
O/B Changeover valve [7]  
Fan relay  
Aux/E Auxiliary/Emergency heat relay  
Sends output when set to Em. Heat [11]  
G
L
See Notes on page 3.  
Thermostat mounting  
1
2
3
. Push excess wire back into the  
wall opening.  
. Plug wall opening with non-  
flammable insulation.  
. Align the 4 tabs on the wallplate  
with corresponding slots on the  
back of the thermostat.  
. Push gently until the thermostat  
snaps in place.  
4
M29386  
4
href="
Installer setup  
Follow the procedure below to configure  
the thermostat to match the installed  
heating/cooling system, and customize  
feature operation as desired.  
1
. To begin, press and hold the s  
and FAN buttons until the display  
changes.  
2
3
. Press s or t to change settings.  
. Press NEXT to advance to next  
function.  
1
0
4
. Press DONE to exit and save  
settings.  
Done  
Next  
Function  
number  
Setting  
Setup function  
Settings & options (factory default in bold)  
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.  
1
System type  
0
1
2
1 heat/1 cool conventional  
1 heat/1 cool heat pump (no aux. heat)  
Heat only — 2-wire systems, 3-wire zone valves (Series 20),  
and normally open zone valves  
3
4
5
6
7
8
9
1
Heat only with fan  
Cool only  
2 heat/1 cool heat pump (with aux. heat)  
2 heat/2 cool conventional  
2 heat/1 cool conventional  
1 heat/2 cool conventional  
2 heat/2 cool heat pump (no aux. heat) - TH5320U only  
3 heat/2 cool heat pump (with aux. heat) - TH5320U only  
0
2
3
Changeover valve  
0
Changeover valve (O/B terminal energized in cooling)  
(
O/B terminal)  
1
Changeover valve (O/B terminal energized in heating)  
Fan control  
0
1
Gas or oil furnace — equipment controls fan in heating  
Electric furnace — thermostat controls fan in heating  
(
heating)  
5
6
Stage 1 heat cycle  
rate  
5
1
3
9
For gas or oil furnaces of less than 90% efficiency  
For steam or gravity systems  
For hot water systems & furnaces of over 90% efficiency  
For electric furnaces  
(
CPH: cycles/hour)*  
Stage 2 heat cycle  
rate/Auxiliary heat  
cycle rate (CPH)*  
5
1
3
9
For gas or oil furnaces of less than 90% efficiency  
For steam or gravity systems  
For hot water systems & furnaces of over 90% efficiency  
For electric furnaces  
7
Auxiliary heat  
cycle rate (CPH)*  
5
1
3
9
For gas or oil furnaces of less than 90% efficiency  
For steam or gravity systems  
For hot water systems & furnaces of over 90% efficiency  
For electric furnaces  
Only TH5320U  
for 3H/2C Heat  
Pumps  
*
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]  
5
href="
Setup function  
Settings & options (factory default in bold)  
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.  
9
Stage 1 compressor 3  
cycle rate (CPH)  
Recommended for most compressors  
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]  
10  
Stage 2 compressor 3  
cycle rate (CPH)  
Recommended for most compressors  
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]  
12  
Manual/Auto  
changeover  
0
1
2
Manual changeover (Heat/Cool/Off)  
Auto changeover (Heat/Cool/Auto/Off)  
Auto changeover only (Auto)  
1
4
5
Temperature  
display  
0
Fahrenheit  
1
Celsius  
1
Compressor  
protection  
5
Five-minute compressor off time  
[Other options: 0, 1, 2, 3 or 4-minute off time]  
26  
Auxiliary heat control0  
Comfort  
Economy  
1
2
7
8
Heat temperature  
range stops  
90 Max. heat temperature setting is 90 °F (32 °C)  
[Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)]  
2
Cool temperature  
range stops  
50 Min. cool temperature setting is 50 °F (10 °C)  
[Other options: 51 °F to 99 °F (10.5 °C to 37 °C)]  
Special function  
Auxiliary heat control (Setup Function 26):  
Comfort Setting: The thermostat will prioritize comfort over economy  
depending on heat pump performance, load conditions and whether the  
thermostat is calling for the heat pump. Raising the temperature just a few  
degrees will often activate the auxiliary heat.  
Economy Setting: The thermostat will attempt to reach the temperature setting  
without activating the auxiliary heat. The thermostat will wait to activate the  
auxiliary heat depending on heat pump performance, load conditions and how  
many degrees the temperature setting is changed.  
6
href="
Installer system test  
1
. To begin, press and hold the  
s and t buttons until the  
display changes.  
2
3
4
. Press s / t to turn system  
on/off.  
. Press NEXT to advance to next  
test  
. Press DONE to terminate  
system test.  
1
0 0  
System  
status  
System test  
number  
System test  
System status  
Shaded areas below apply only to TH5320U/TH5220D or as otherwise noted.  
10  
Heating system  
0
1
Heat and fan turn off.  
Stage 1 heat turns on. Fan turns on if Setup Function 1 is  
set to 1, 5, 9 or 10 OR Setup Function 3 is set to 1  
Stage 2 heat turns on  
2
3
Stage 3 heat turns on - TH5320U only  
2
0
0
Emergency heating  
system  
0
1
Heat and fan turn off  
Heat and fan turn on  
3
Cooling system  
0
1
2
Compressor and fan turn off  
Compressor and fan turn on  
Stage 2 compressor turns on  
40  
Fan system  
0
1
Fan turns off  
Fan turns on  
Specifications  
Temperature Ranges  
Electrical Ratings  
Heat: 40° to 90°F (4.5° to 32°C)  
Cool: 50° to 99°F (10° to 37°C)  
Operating Ambient Temperature  
Terminal  
W Heating  
(Powerpile)  
Voltage (50/60Hz)  
20-30 Vac  
750 mV DC  
Running Current  
0.02-1.0 A  
100 mA DC  
0.02-1.0 A  
0.02-1.0 A  
0.02-1.0 A  
0.02-0.5 A  
0.02-0.5 A  
0.02-0.5 A  
3
2° to 120°F (0° to 48.9°C)  
Shipping Temperature  
20° to 120°F (-28.9° to 48.9°C)  
Operating Relative Humidity  
% to 90% (non-condensing)  
W2 (Aux/E) Heating 20-30 Vac  
Y Cooling  
Y2 Coo