800 SERIES EC7895A, RM7895A  
Relay Module  
PRODUCT DATA  
Dependable, long-term operation provided by microcomputer  
technology.  
First-out annunciation and system diagnostics provided by a 2  
row by 20 column Vacuum Fluorescent Display (VFD) located  
on the optional Keyboard Display Module.  
Five (LEDs) for sequence information.  
Interchangeable plug-in flame amplifiers.  
Local or remote annunciation of EC7895 and RM7895  
operation and fault information.  
Nonvolatile memory; EC7895 and RM7895 retain history files  
and sequencing status after loss of power.  
Remote reset (optional).  
Report generation (optional).  
Selectable recycle or lockout on loss of airflow.  
Selectable recycle or lockout on loss of flame.  
Shutter drive output.  
Burner controller data (optional):  
Flame signal strength.  
Hold status.  
Lockout/alarm status.  
Sequence status.  
Sequence time.  
Total cycles of operation.  
Total hours of operation.  
Fault history providing for the six most recent faults:  
GENERAL  
Cycles of operation at the time of the fault.  
Fault message and code.  
Hours of operation at the time of the fault.  
Sequence status at the time of the fault.  
Sequence time at the time of the fault.  
The Yamatake Honeywell EC7895A and RM7895 is a microprocessor  
based integrated burner control for automatically fired gas, oil, or  
combination fuel single burner applications. The RM7895 consists of  
the Relay Module. Subbase, Amplifier and Purge Card. Options  
include Keyboard Display Module, Personal Computer Interface,  
DATA CONTROLBUS MODULE™, Remote Display Module, and  
COMBUSTION SYSTEM MANAGER™ Software.  
Diagnostic information:  
Device type.  
Flame amplifier type.  
Flame failure response time.  
Manufacturing code.  
On/Off status of all digital inputs and outputs.  
Selected prepurge time.  
Software revision and version of EC7895 and RM7895  
and optional Keyboard Display Module.  
Status of configuration jumpers.  
The EC7895 and RM7895 are programmed to provide a level of  
safety, functional capability and features beyond the capacity of  
conventional controls.  
Functions provided by the EC7895 and RM7895 include automatic  
burner sequencing, flame supervision, system status indication,  
system or self-diagnostics and troubleshooting.  
Contents  
FEATURES  
General .........................................................................................  
Features ........................................................................................  
Specifications ................................................................................  
Ordering Information .....................................................................  
Principal Technical Features .........................................................  
Safety Provisions ..........................................................................  
Installation .....................................................................................  
Wiring ............................................................................................ 11  
Assembly ...................................................................................... 14  
Operation ...................................................................................... 17  
Checkout ....................................................................................... 20  
Troubleshooting ............................................................................ 26  
1
1
2
2
8
8
9
Safety features:  
Airflow switch check.  
Closed loop logic test.  
Dynamic AMPLI-CHECK®.  
Dynamic input check.  
Dynamic safety relay test.  
Dynamic self-check logic.  
Internal hardware status monitoring.  
Tamper resistant timing and logic.  
Access for external electrical voltage checks.  
Application flexibility.  
Communication interface capability.  
Copyright © 1996 Honeywell Inc.  
All Rights Reserved  
65-0205  
href="
7800 SERIES EC7895A, RM7895A RELAY MODULE  
Electrical Ratings, see Table 1A:  
SPECIFICATIONS  
Voltage and Frequency: 100 Vac (+10/-15%), 50 or 60 Hz  
1
(+/- 10%).  
Model:  
RM7895A  
Power Dissipation: RM7895: 10W maximum.  
Maximum Total Connected Load: 2000 VA.  
Fusing Total Connected Load: 20A maximum, type FRN or  
equivalent.  
Table 1A. RM7895A Terminal Ratings.  
Terminal No.  
Description  
Ratings  
G
Flame Sensor Ground  
2
Earth G  
Earth Ground  
L2(N)  
Line Voltage Common  
Alarm  
3
4
5
6
7
8
9
100 Vac, 1A pilot duty.  
Burner Motor  
Line Voltage Supply (L1)  
Burner Controller and Limits  
Airflow Interlock  
Pilot Valve/Ignition  
Main Fuel Valve  
Ignition  
100 Vac, 9.8 AFL, 58.8 ALR (inrush).  
100 Vac (+10/-15%), 50 or 60 Hz (+/- 10%).  
100 Vac, 1 mA.  
3,4  
100 Vac, 9A.  
100 Vac, 4.5A ignition and 50VA pilot duty.  
100 Vac, 2A pilot duty.  
100 Vac, 4.5A ignition.  
4
5
4
10  
F(11)  
Flame Sensor  
Unused  
60 to 220 Vac, current limited.  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
Shutter  
100 Vac, 0.5A  
1
2
Range of allowable operating frequency: 45 to 66 Hz.  
The 7895 must have an earth ground providing a connection between the subbase and the control panel or the equipment.  
The earth ground wire must be capable of conducting the current to blow the 20A fuse (or breaker) in event of an internal short  
circuit. The 7895 needs a low impedance ground connection to the equipment frame which, in turn, needs a low impedance  
connection to earth ground. For a ground path to be low impedance at RF frequencies, the connection must be made with  
minimum length conductors that have maximum surface areas. Wide straps or brackets rather than leadwires are preferred.  
Be careful to verify that mechanically tightened joints along the ground path, such as pipe or conduit threads or surfaces held  
together with fasteners, are free of nonconductive coatings and are protected against mating surface corrosion.  
3
2
000 VA maximum connected load to 7895 Assembly.  
4
5
Can also be 100 Vac, 1A pilot duty.  
Can also be 65 VA pilot duty with motorized valve, 1150 VA inrush, 460 VA open, 250 VA hold.  
ORDERING INFORMATION  
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the  
TRADELINE® Catalog or price sheets for complete ordering number.  
If you have additional questions, need further information, or would like to comment on our products or services, please write or  
phone:  
1
2
.
.
Your local Home and Building Control Sales Office (check white pages of your phone directory).  
Home and Building Control Customer Relations  
Honeywell, 1885 Douglas Drive North  
Minneapolis, Minnesota 55422-4386  
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.  
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,  
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.  
65-0205  
2
href="
7800 SERIES EC7895A, RM7895A RELAY MODULE  
Model:  
EC7895  
Electrical Ratings, see Table 1B:  
Voltage and Frequency: 200 Vac (+10/-15%), 50 or 60 Hz  
1
(+/- 10%).  
Power Dissipation: EC7895: 10W maximum.  
Maximum Total Connected Load: 2000 VA.  
Fusing Total Connected Load: 20A maximum, type FRN or  
equivalent.  
Table 1B. EC7895A Terminal Ratings.  
Terminal No.  
Description  
Flame Sensor Ground  
Earth Ground2  
Line Voltage Common  
Alarm  
Ratings  
G
Earth G  
L2 (N)  
3
4
5
6
7
8
9
200 Vac, 1A pilot duty.  
Burner Motor  
Line Voltage Supply (L1)  
Burner Controller and Limits  
Airflow Interlock  
Pilot Valve/Ignition  
Main Fuel Valve  
Ignition  
200 Vac, 4A at pF = 0.5, 20A inrush4  
200 Vac (+10/-15%), 50 or 60 Hz (+/- 10%).3,4  
200 Vac, 1 mA.  
200 Vac, 9A.  
200 Vac, 4A at pF = 0.5, 20A inrush4  
200 Vac, 4A at pF = 0.5, 20A inrush4  
200 Vac, 4A at pF = 0.5, 20A inrush4  
60 to 220 Vac, current limited.  
10  
F(11)  
Flame Sensor  
Unused  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
Shutter  
200 Vac, 0.5A  
1
Range of allowable operating frequency 45 through 66 Hz.  
2
The EC7895 must have an earth ground providing a connection between the subbase and the control panel or the equipment.  
The earth ground wire must be capable of conducting the current to blow the 20A fuse (or breaker) in event of an internal short  
circuit. The RM7895 needs a low impedance ground connection to the equipment frame which, in turn, needs a low  
impedance connection to earth ground. For a ground path to be low impedance at RF frequencies, the connection must be  
made with minimum length conductors that have maximum surface areas. Wide straps or brackets rather than leadwires are  
preferred. Be careful to verify that mechanically tightened joints along the ground path, such as pipe or conduit threads or  
surfaces held together with fasteners, are free of nonconductive coatings and are protected against mating surface corrosion.  
3
2
000 VA maximum connected load to EC7895 Assembly.  
Total load current excluding burner/boiler motor and firing rate outputs cannot exceed 5A, 25A inrush.  
4
3
65-0205  
href="
7800 SERIES EC7895A, RM7895A RELAY MODULE  
Environmental Ratings:  
Weight:  
Ambient Temperature:  
RM7895 with Dust Cover: 1 pound 15 ounces, unpacked.  
Operating: -40° F to 140° F.  
Storage: -60° F to 150° F.  
Humidity: 85% RH continuous, noncondensing.  
Vibration: 0.5G environment.  
IMPORTANT  
Flame Detection System available for use with  
EC7895 and RM7895. To select your Plug-in Flame  
Signal Amplifier and applicable Flame Detector, see  
Table 2 and Fig. 3 through 5.  
Dimensions:  
Refer to Fig. 1 and 2.  
Table 2. Flame detection systems (Figs. 3, 4, 5).  
Plug-in Flame Signal Amplifiers  
Applicable Flame Detectors  
Flame  
Failure  
Response  
Time  
Self-  
Checking  
No  
Type  
Color  
Model  
Fuel  
Gas  
Type  
Models  
Rectification  
Green  
R7847A  
.8 or 3 sec  
Rectifying Flame C7004, C7007, C7011  
Rod Holders  
a
Complete Assemblies:  
C7008, C7009, Q179.  
No  
No  
R7847A  
R7847A  
R7847Bd  
.8 or 3 sec  
3 sec  
Oil  
Rectifying  
Photocell  
C7003, C7010, C7013,  
C7014  
C7012A,C.c  
b
Gas,  
Ultraviolet  
Oil, Coal (Purple Peeper)  
Dynamic  
AMPLI-  
CHECK®  
.8 or 3 sec  
Gas  
Rectifying Flame C7004, C7007, C7011  
a
Rod Holders Complete Assemblies:  
C7008, C7009, Q179.  
Dynamic  
AMPLI-  
CHECK®  
R7847Bd  
R7847Bd  
.8 or 3 sec  
3 sec  
Oil  
Rectifying  
Photocell  
C7003, C7010, C7013,  
C7014  
b
Dynamic  
AMPLI-  
Gas,  
Ultraviolet  
C7012A,C.c  
Oil, Coal (Purple Peeper)  
CHECK®  
Dynamic  
Self-Check  
R7847Ce  
R7848A  
R7848Bd  
3 sec  
3 sec  
3 sec  
Gas,  
Oil, Coal (Purple Peeper)  
Gas, Infrared  
Oil, Coal (Lead Sulfide)  
Gas, Infrared  
Ultraviolet  
C7012E,F.  
C7015  
Infrared  
Red  
No  
Dynamic  
AMPLI-  
C7015  
Oil, Coal (Lead Sulfide)  
CHECK®  
Ultraviolet  
Purple  
No  
R7849A  
.8 or 3 sec  
.8 or 3 sec  
Gas, Oil Ultraviolet  
C7027, C7035,  
C7044.  
c
(MiniPeeper)  
Dynamic  
AMPLI-  
R7849Bd  
Gas, Oil Ultraviolet  
(MiniPeeper)  
C7027, C7035,  
c
C7044.  
CHECK®  
Dynamic  
Self-Check  
R7861A  
3 sec  
3 sec  
Gas,  
Oil, Coal  
Ultraviolet  
Ultraviolet  
C7061  
C7076  
f
Blue  
Dynamic  
Self-Check  
R7886Ae  
Gas,  
g
Oil, Coal (Adjustable  
Sensitivity)  
a
b
c
Order flame rod separately; see holder Instructions.  
Use only Honeywell Photocell, part no. 38316.  
The C7012A,C, C7027, C7035 and C7044 Flame Detectors should be used only on burners that cycle on-off at least once  
every twenty-four hours. Appliances with burners that remain on continuously for twenty-four hours or longer should use the  
C7012E,F Flame Detector with the R7847C Amplifier or the C7076A,D Flame Detector with the R7886A Amplifier or the C7061  
Flame detector with the R7861 Amplifier as the ultraviolet flame detection system.  
Circuitry tests the flame signal amplifier at least 12 times a minute during burner operation and shuts down the burner if the  
amplifier fails.  
Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute during burner  
operation and shuts down the burner if the detection system fails.  
When R7861 is used with EC7895, the application requires a step down transformer. See Fig. 14.  
Use with RM7895A only.  
d
e
f
g
65-0205  
4
href="
7800 SERIES EC7895A, RM7895A RELAY MODULE  
Sequence Timing For Normal Operation:  
Flame Establishing Period  
Device  
Initiate  
Standby  
Purge  
Pilot  
Main  
No  
EC7895A/RM7895A  
10 sec.  
*
**  
4 or 10 sec.  
*
*
STANDBY and RUN can be an infinite time period.  
* PURGE is determined by the ST7800A Purge Card selected.  
Approval Bodies:  
Accessories:  
RM7895A:  
Optional:  
Underwriters Laboratories Inc. listed: File no. MP268,  
Guide no. MCCZ.  
Network Interface Unit,  
Part No. Q7700A1014, 120V 50/60 Hz  
Factory Mutual approved.  
EC7895A:  
Factory Mutual approved.  
Part No. Q7700B1004, 100V to 200V 50/60 Hz  
Network Interface ControlBus Module,  
Part No. QS7800A1001.  
COMBUSTION SYSTEM MANAGER™,  
Mounting:  
Part No. ZM7850A1001.  
Q7800A for panel mount or Q7800B for wall or burner mount.  
ControlBus 5-Wire Electrical Connector,  
Part No. 203541.  
Required Components:  
DATA CONTROLBUS MODULE™,  
Part No. S7810A1009.  
Dust Cover, Part No. 221729A.  
Plug-in Flame Signal Amplifier, see Table 2.  
Plug-in Purge Timer Cards: Selectable ST7800A, two  
seconds to 30 minutes.  
Flame Simulators:  
Q7800A or Q7800B.  
UV Flame Simulator, Part No. 203659.  
Rectification Simulator, Part No. 123514A.  
Keyboard Display Module, Part No. S7800A1001,  
English.  
Keyboard Display Module, Part No. S7800A1118,  
Japanese.  
Remote Display Mounting Bracket, Part No. 203765.  
Remote Display Power Supply, Part No. 203968A Plug-in.  
Remote Reset Module, Part No. 57820A1007.  
Sixty-inch Extension Cable Assembly, Part No. 221818A.  
BURNER  
CONTROL  
5
127)  
1
(
POWER  
PILOT  
FLAME  
MAIN  
ALARM  
RESET  
5
-1/4 (133)  
5
(127)  
M11135  
1
REMOVE ONLY FOR TERMINAL TEST ACCESS.  
Fig. 1. Mounting dimensions of EC7895/RM7895 Relay Module and Q7800A Subbase in in. (mm).  
5
65-0205  
href="
7800 SERIES EC7895A, RM7895A RELAY MODULE  
BURNER  
CONTROL  
5
(
127)  
POWER  
PILOT  
FLAME  
MAIN  
1
ALARM  
RESET  
6-3/32 (155)  
5
(127)  
1
REMOVE ONLY FOR TERMINAL TEST ACCESS.  
M11134  
Fig. 2. Mounting dimensions of EC7895/RM7895 Relay Module and Q7800B Subbase in in. (mm).  
IGNITION  
ELECTRODE  
FLAME ROD  
(Q179C ONLY)  
CERAMIC  
INSULATORS  
1
(25)  
1
-21/32  
1-13/32  
(36)  
(42)  
TARGET  
/8 (10)  
MOUNTING FLANGE  
-7/32  
183)  
3/4–14 NPT  
3
7
(
5-1/8 (130)  
3
(
-1/8  
79)  
1
-1/16  
3-3/4  
95)  
(27)  
1/2 (13)  
(
3-7/16  
(87)  
3/32 (2)  
11/16  
(
18)  
2
(
5/32  
20)  
25/32  
(20)  
1
(
7/32  
14)  
THREADED  
MOUNTING  
HOLES (2)–  
10-32 UNF  
1/2–14 NPSM  
5-1/4 (133)  
2
-25/32  
62)  
LEADWIRES  
(
FACEPLATE  
M1962A  
BRACKET  
M1983  
Q179  
C7012A,C,E,F  
13/16 (21)  
1-1/4 (32)  
1-3/8 (35)  
2
(
51)  
1
(
-3/4  
45)  
1-1/4 (32)  
1-5/16 (33)  
5
(
/16  
8)  
C7013A  
C7014A  
M1847  
Fig. 3. Rectification detectors.  
65-0205  
6
href="
7800 SERIES EC7895A, RM7895A RELAY MODULE  
4-1/8 (105)  
COLLAR WITH  
–11-1/2 NPSM  
2 (51)  
-3/16  
(30)  
1/2-14 NPSM  
INTERNAL THREADS  
2
1
1
INTERNAL  
THREADS  
1
4
(102)  
6 FOOT (1.83 METER)  
LEADWIRES (2)  
3-1/2 (89)  
1
3
1/32  
1
(
-1/2 (25)  
38)  
1-1/16  
(27)  
2
6
[
FOOT  
1.83 METER]  
LEADWIRES (2)  
2-5/8 (67)  
INSERTION DEPTH  
3
COLLAR WITH 1/2-14 NPSM  
INTERNAL THREADS  
1
2
3
DIN APPROVED C7035A1064 HAS 1-11 BSP.P1 INTERNAL THREADS.  
DIN APPROVED C7035A1064 HAS 1/2-14 BSP-F INTERNAL THREADS.  
1
2
MODEL AVAILABLE WITH 24 FOOT (7.32 METER) LEADWIRES.  
MODELS AVAILABLE WITH SPUD CONNECTOR (1/2-14 NPSM INTERNAL  
THREADS) INSTEAD OF CLAMP TYPE CONNECTOR.  
M1943A  
MODEL AVAILABLE WITH 12 FOOT [3.66 METER] LEADWIRES.  
M1945A  
C7027  
C7035  
6
FOOT [1.83 METER]  
LEADWIRES (2)  
MOUNTING BRACKET  
3/8  
(10)  
7/8  
(22)  
9/16  
(14)  
1/2  
(13)  
1-27/64