Home

href="
L7224A,C; L7248A,C,L  
Oil Electronic  
®
Aquastat Controllers  
INSTALLATION INSTRUCTIONS  
APPLICATION  
SPECIFICATIONS  
The L7224A,C and L7248A,C,L 2012 Compliant Oil  
Electronic Aquastat® Controllers provide electronic  
temperature sensing in a UL limit-rated control with a  
single sensing probe. The L7224A,C and L7248A,C,L  
control the circulator, oil burner and boiler temperature.  
The L7224/L7248 is “Outdoor Temperature Reset” ready  
which is enabled when connected to the W8735S1000  
Outdoor Reset Kit. Outdoor Reset with the L7224/L7248  
is intended for all applications except for tankless coil  
systems for domestic hot water. Compliance to 2012  
DOE regulation ensures efficiency is maximized without  
interfering with domestic hot water demand.  
Electrical Ratings:  
Voltage: 120 Vac, 60 Hz.  
Power: 7 VA maximum at 120 Vac plus external loads.  
Thermostat current: 100 mA nominal at 24 Vac.  
Burner Relay:  
7.4 A at 120 Vac Full Load Amperage (FLA);  
44.4 A inrush Locked Rotor Amperage (LRA);  
Less Ignition Load: 360 VA.  
Circulator Relay:  
7.4 A at 120 Vac FLA; 44.4 A inrush LRA.  
Zone Controller (ZC): 7.4 A at 120 Vac FLA;  
44.4 A inrush LRA.  
The L7224A,C and L7248A,C,L replace the L8124A,  
L8124C, L7124A,C, L7148A and L8148A Controllers.  
The L7224A,C and L7248A,C,L series controls provide  
status and diagnostic information through an LED display  
combined with LED lights as well as EnviraCOM™  
communications enabled thermostats and diagnostic  
tools to enhance the diagnostic process.  
NOTE: All loads combined cannot exceed 2000 VA.  
Environmental Ratings:  
Temperature: -30 °F to +150 °F (-34 °C to +66 °C).  
Humidity: 0 to 95% relative humidity, noncondensing.  
Approvals:  
Underwriters Laboratories Inc. Component Recognized.  
Canadian Underwriters Laboratories Inc. Component  
Recognized.  
L7224/L7248 Aquastat Controllers are intended for use  
in residential-type applications.  
IMPORTANT  
Use of Outdoor Temperature Reset on a tank-  
less coil application requiring a Low Limit setting  
will result in reduced system effectiveness and  
efficiency.  
2012 DOE Compliance and Operation  
Operation of this control may delay the burner operation while the residual heat is  
circulated out of the boiler.  
NOTE: This operation may be different than earlier electronic Aquastat®  
revisions which did not implement thermal purge.  
6
8-0281EFS-05  
href="
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS  
Accessories:  
INSTALLATION  
W8735Y1000 Wireless Outdoor Reset Kit  
W873ER1000 Wireless Outdoor Reset Module  
C7089R1013 Wireless Outdoor Temperature Sensor  
When Installing this Product...  
1. Read these instructions carefully. Failure to follow  
them could damage the product or cause a  
hazardous condition.  
(
requires W8735ER1000)  
W8735S1000 AquaReset™ Outdoor Reset Kit (includes  
0022037-002 Outdoor Reset Module and  
5
C7089U1006 Outdoor Temperature Sensor)  
W8735S1008 AquaReset™ Domestic Hot Water Kit  
2. Check the ratings given in the instructions and on  
the product to make sure the product is suitable for  
your application.  
3. The installer must be a trained, experienced service  
technician.  
(
includes 50022037-005 Domestic Hot Water Module  
and 32003971-003 Sensor)  
W8735S3000 EnviraCOM™ Alarm Module  
C7089U1006 Outdoor Temperature Sensor (used with the  
5
0022037-002)  
2003971-003 Temperature Sensor (used with  
0022037-005)  
Sensor (See Table 2).  
4. After installation is complete, check out product  
operation as provided in these instructions.  
5. Set High Limit, Low Limit and Low Limit Differential  
to the settings recommended by the boiler OEM.  
6. Record the maximum High Limit setting from the  
replaced controller in the text box provided on the  
cover insert label.  
3
5
1
4,000,485-016 1/4 in. (6.35 mm) diameter, 1-1/4 in.  
(31.75 mm) long glass cartridge Fuse, 1A, Slow-Blow.  
1
1
20650 Heat Conductive Compound.  
21371AA Sensor Well Clamp.  
7. Record the High Limit setting at time of installation  
in the text box provided on the cover insert label.  
Table 1. Wells for L7224A,C; L7248A,C,L Controllers.  
Part  
Spud Size  
in. (mm)  
Insertion Insulation  
in. (mm) in. (mm)  
1-1/2 (38.1)  
1-1/2 (38.1)  
WARNING  
Number  
Electrical Shock Hazard.  
Can cause severe injury, death or property  
damage.  
1
23869A 1/2 (12.7) NPT 3 (76.2)  
23870A 3/4 (19.05) NPT 3 (76.2)  
1
Disconnect power supply before beginning  
installation to prevent electrical shock or  
equipment damage.  
Table 2. Sensors for L7224A,C and  
L7248A,C,L Controllers.  
Mounting  
Length in.  
(mm)  
Part Number  
Application  
The L7224A,C and L7248A,C,L models are available in a  
well-mount, horizontal position, vertical position, or flush  
mounted remote from the well versions. Dimensions for  
the variety of mounting options are shown in Fig. 1. Note  
that each identity will have only a single mounting option.  
5
0001464-001  
0001464-003  
0001464-004  
0001464-005  
12 (304.8) Well-mounted controls  
24 (609.6) Flush-mounted controls  
36 (914.4)  
5
5
5
48 (1219.2)  
3
/4  
75)  
(
7
-1/8  
181)  
(
6
-1/2  
166)  
(
5
(
-11/16  
145)  
3
(
-1/32  
77)  
3
/8  
1-3/16  
(30)  
(
10)  
1
-1/8 (29)  
2
-1/16 (53)  
2
-5/8 (67)  
1/16 (2)  
4
-1/4 (109)  
3-13/32 (86)  
2
x 1/4 (7) x 3/8 (9)  
M22147B  
Fig. 1. L7224A,C; L7248A,C,L mounting dimensions in inches (mm).  
68-0281EFS—05  
2
href="
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS  
IMPORTANT  
Immersion well must fit sensing element and  
sensor must rest against bottom of well.  
SENSOR WIRES  
CONTROLLER CASE  
BOILER  
New Installation  
IMMERSION  
WELL  
SENSOR  
Order well assemblies separately; see Table 1 and form  
no. 68-0040, Immersion Wells and Compression Fittings  
for Temperature Controllers. Boilers usually have tappings  
that allow the well to be mounted horizontally so boiler  
water of average temperature can circulate freely over the  
well.  
HEAT-CONDUCTIVE COMPOUND  
OPTIONAL)  
(
1
.
Turn off all power and drain the boiler, if applicable.  
If no tapping is provided, prepare properly sized and  
threaded tapping near the top of the boiler.  
2
.
IMMERSION  
WELL CLAMP  
M16120  
3.  
Sparingly coat the well threads with pipe dope.  
IMMERSION WELL  
CLAMP SCREW  
NOTE: Do not attempt to tighten by using the case  
as a handle.  
Fig. 2. Position of sensor in immersion well.  
4.  
Install the well in the boiler tapping and tighten  
securely.  
Flush-Mounted Aquastat  
Replacement  
Turn off all power and remove the old control. Refer to the  
cover insert of the old control to identify and tag each  
external lead as it is disconnected. If the old well is  
unsuitable for the new installation, remove it and replace it  
with a suitable new well. If the old well is suitable, use it.  
5
6
7
.
.
.
Refill boiler and check for water leakage.  
Loosen but do not remove the well clamp screw.  
Fit the case into the well so the clamp on the case  
slides over the flange on the well.  
8
.
.
Securely tighten the clamp screw.  
9
Insert the sensor element into the well until it bot-  
toms. See Replacement Sensor Installation section  
for details. (If necessary, slightly bend the wire  
inside the case to hold the sensor against the bot-  
tom of the well.)  
1
1
0. Turn power ON.  
1. Set High Limit, Low Limit and Low Limit Differential  
to the settings recommended by the boiler OEM.  
Well-Mounted Aquastat  
Replacement  
Turn off all power and remove the old control. Refer to the  
cover insert of the old control to identify and tag each  
external lead as it is disconnected. If the old well is  
unsuitable for the new installation, remove it and proceed  
with instructions for new installation. If the old well is  
suitable, use it.  
(
See OPERATION section.) (See INSTALLATION  
steps 6 and 7.)  
1
2. On L7248L models, adjust ELL option to match your  
configuration (see OPERATION section, and Fig. 11  
and 13).  
IMPORTANT  
Best thermal response is obtained with a well  
1
2
3
.
.
.
Loosen, but do not remove, the well clamp screw on  
the side of the control case.  
Position immersion well clamp snugly over the  
flange of the adapter and tighten the clamp screw.  
Insert the sensor into the well as shown in Fig. 2 or  
that snugly fits the sensor. Insert the sensor until  
it rests against the bottom of the well. Use a well  
of correct length and bend the wiring, if neces-  
sary, to hold the bulb against the bottom of the  
well.  
3
. (See Replacement Sensor Installation section for  
details.)  
If the well is not a snug fit on the sensor, use the  
heat-conductive compound (furnished with  
TRADELINE® models) as follows: Fold the  
THERMOSTAT  
TERMINALS  
DISPLAY  
plastic bag of compound lengthwise and twist it  
gently. Then snip off end of bag and work the  
open end of the bag all the way into the well.  
Slowly pull out the bag while squeezing it firmly  
to distribute compound evenly in the well. Bend  
the wiring, if necessary, to hold the sensor  
against the bottom of the well and to hold outer  
end of the sensor in firm contact with the side of  
the well. See Fig. 2. Wipe excess compound  
from the outer end of the well.  
FUSE  
L I N E  
TM  
SENSOR  
ENVIRACOM  
SENSOR HOLES  
TERMINALS  
CONNECTOR  
M32186  
Fig. 3. Circuit board, showing sensor connection and  
well holes for horizontal mount models.  
3
68-0281EFS—05  
href="
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS  
WIRING  
SENSOR WIRES  
BOILER  
WARNING  
Electrical Shock Hazard.  
IMMERSION  
WELL  
SENSOR  
Can cause serious injury or death.  
Disconnect power supply before making wiring  
connections to prevent electrical shock or  
equipment damage.  
HEAT-CONDUCTIVE COMPOUND  
OPTIONAL)  
All wiring must comply with local electrical codes and  
ordinances. Do not exceed the specifications in the  
Application section when wiring this control. Use wire  
rated for 194 °F (90 °C) or higher.  
(
M22026  
Fig. 4. Replacement sensor installation.  
IMPORTANT  
The terminals on these Aquastat Controllers are  
approved for use with copper wire only.  
Replacement Sensor Installation  
Follow the appropriate wiring diagrams shown on the  
inside of the front cover of the L7224A,C; L7248A,C,L or  
in Fig. 8–13.  
Turn off all power and:  
1.  
2.  
3.  
Carefully disconnect sensor from circuit board by  
pulling gently on the connector.  
Gently pull sensor from thermo well and through cir- Refer to Fig. 6 for Connections for the optional Outdoor  
cuit board by pulling on leadwires.  
Reset Module and the Domestic Hot Water (DHW)  
module. In subsequent wiring diagrams these modules  
will be displayed with a dotted line signifying that they are  
optional.  
Carefully align replacement sensor with hole in cir-  
cuit board and guide through Aquastat case and  
into well. (See Fig. 5).  
4.  
5.  
6.  
Make sure sensor is fully seated to bottom of well  
(
See Fig. 4). Use a small pencil to measure depth of  
5
0022037-002  
sensor in well, if necessary.  
OUTDOOR  
RESET MODULE  
Connect sensor to circuit board by pressing con-  
nector on sensor unit into mating connector on cir-  
cuit board (See Fig. 5).  
For remote sensors (flush-mounted Aquastat Con-  
trollers) be sure to use 121571AA Clamp (see  
Accessories) to securely hold sensor in place.  
T
T
1 2 3 OT OT  
3
2
1
C7089U1006  
TM  
OUTDOOR  
SENSOR  
THERMOSTAT  
TERMINALS  
ENVIRACOM  
TERMINALS  
ZR  
L1  
5
0022037-005  
DOMESTIC HOT  
WATER MODULE  
T
L2  
T
3
2
1
C2  
B2  
C1  
B1  
ZC  
1
2 3 TS TS  
DISPLAY  
3
2003971-003  
TEMPERATURE  
SENSOR  
M29651  
ZR  
L1  
L2  
SENSOR  
CONNECTOR  
Fig. 6. Wiring the Outdoor Reset Module and the  
Domestic Hot Water Module.  
C2  
B2  
C1  
B1  
ZC  
RELAYS  
SENSOR HOLES  
FUSE  
OPERATION  
General  
M32187  
The L7224A,C and L7248A,C,L Oil Electronic Aquastat  
Controllers are primary safety limit-rated devices  
designed for use with oil fired boilers with line voltage  
burners and circulators. Many boilers do not include  
wiring or control compartments as part of the design, but  
are provided with an integral, replaceable, immersion well  
that is the mounting hardware for the Aquastat  
Controllers. Wiring to the other controls is done through  
flexible metal conduit.  
Fig. 5. Circuit board, showing sensor connection and  
well holes for vertical mount models.  
Fuse  
The 1 Amp fuse located near the transformer is intended  
to protect the EnviraCOM circuit from incorrect wiring. The  
Aquastat will continue to function should the fuse blow or  
be removed though no EnviraCOM communication will be  
possible on the bus and Err 6 will be displayed. See  
Table 10.  
For boilers that do include a remotely (flush) mounted  
control, the wiring may be completed with conduit or  
routed behind the boiler sheet metal.  
68-0281EFS—05  
4
href="
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS  
A separate electromechanical high-limit is not required in  
a system that uses this control to meet Underwriters  
Laboratories Inc. requirements for oil-fired boiler  
assemblies, UL 726.  
Table 3. Adjustable Features.  
Display  
HL_  
Hdf  
Definition  
High Limit.  
On the L7224 models, the High Limit, Low Limit, Low Limit  
Differential, and Anti Short-Cycle time can be adjusted to  
the setting recommended by the boiler OEM. On the  
L7248 models, the High Limit, and Anti Short-Cycle time  
are also adjustable, see “Adjusting Settings”.  
High Limit Differential.  
LL_  
Low Limit. (L7224A, C)  
Ldf  
Low Limit Differential (L7224A, C)  
External Low Limit (L7248L only)  
ELL  
duu  
The overall range of the High Limit is from 130 °F to  
2
40 °F (54 °C to 116 °C). Select devices may have  
ZR input configured as external Domestic Hot  
Water (DHW) request (ON/OFF) (L7224A,C/  
L7248L)  
different ranges. Some models have limited ranges on the  
High Limit setpoint; this limited range is listed on the  
device label.  
ASC  
otL*  
otH*  
btL*  
bP*  
Anti Short-Cycle Timeout (seconds); “OFF” is  
disabled.  
Some models also have a Low Limit and Low Limit  
Differential adjustment. The range of the Low Limit is from  
Outdoor Temperature Low (minimum)  
parameter for the outdoor reset curve (°F or °C)  
110 °F to 220 °F (43 °C to 104 °C). Select devices may  
have different ranges.  
Outdoor Temperature High (maximum)  
parameter for outdoor reset curve (°F or °C)  
The Zr setting can be set to DHW, Zoning, or for tankless  
coil applications depending on the L7224/L7248.  
Boiler Temperature Low (minimum) parameter  
for outdoor reset curve  
If a W8735S1000 AquaReset™ Outdoor Reset Module is  
installed, the reset curve can be set by entering the  
minimum outdoor temperature, minimum (boiler)  
temperature, and maximum outdoor temperature on the  
Boost Period (minutes). “OFF” is displayed if  
Boost is inactive  
bS*  
Boost step (°F or °C) shown only if Boost is  
active (bP=ON)  
3-digit display. The range of the minimum outdoor  
temperature is from -40 °F to 40 °F (-40 °C to 4.4 °C) and  
has a default setting of 0 °F (-18 °C). The range of the  
maximum outdoor temperature is from 30 °F to 70 °F  
UUS*  
tPL**  
tPt**  
Warm Weather Shutdown Temperature  
(
°F or °C)  
Thermal Purging Limit Temperature (°F or °C),  
OFF” if disabled  
(
-1.1 °C to 21.1 °C) and has a default setting of 40 °F. The  
range of the minimum (water or boiler) temperature is  
from 80 °F to 180 °F (26.7 °C to 82.2 °C) and has a  
default setting of 130 °F. See the “Outdoor Reset Module”  
Installation Instructions (form number 69-2335) for more  
information on setting the boiler reset curve and all related  
parameters.  
Termal Purging Time Delay (minutes), shown  
only if tPL is enabled  
PC  
Pump Cycling (ON / OFF)  
Temperature units (°F or °C)  
F-C  
*
*
Settings available for adjustment on the 3-digit display  
only if the W8735S1000 AquaReset Outdoor Reset  
Module is installed.  
*Settings available for adjustment only when the  
W8735S1000 AquaReset Outdoor Reset Kit is NOT  
installed.  
The L7224A,C and L7248A,C,L are designed for use with  
2
4 Vac electronic and electromechanical thermostats or  
EnviraCOM™ enabled thermostats, and have screw-type  
terminals for easy field connection.  
Adjusting Settings  
Then press the UP and/or DOWN buttons to move the set  
point to the desired value, to change between °F and °C,  
or to enable (On) or disable (Off) the External Low Limit.  
After 60 seconds without any button inputs, the control will  
automatically return to the RUN mode.  
To discourage unauthorized changing of Aquastat  
settings, a procedure to enter the ADJUSTMENT mode is  
required. To enter the ADJUSTMENT mode, press the  
UP, DOWN, and I buttons (Refer to Fig. 5) simultaneously  
for three seconds. Press the I button until the feature  
requiring adjustment is displayed:  
Display  
In the RUN mode, the Aquastat will flash “bt” (boiler temp)  
followed by the temperature (i.e., 220), followed by °F or  
°
C.  
To read boiler settings, press the I key to read the  
parameter of interest. For example, press I and High Limit  
(
2
HL) is displayed, followed by a three-digit number, i.e.,  
20, followed by °F or °C. Pressing the I button again (on  
L7224 models) will display the Low Limit (LL) followed by  
a three-digit number and the corresponding degree  
designator. See Display Readout, Table 4.  
After approximately 60 seconds without any key presses,  
the display will enter a dim display mode. To return to the  
bright display mode, simply press any key.  
5
68-0281EFS—05  
href="
L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT® CONTROLLERS  
has not gone below the Low Limit setting (minus the  
Differential); or, ZR input is not powered with 120  
Vac (only L7248L with ELL set On).  
Table 4. Display readout definitions.  
Text  
Err  
Description  
Display  
2. High Limit: Boiler temperature went above the High  
Limit setting and has not dropped below the High  
Limit setting (minus the Differential).  
Error Code (if one is present)  
  
3
.
Low Limit: Boiler temperature went below the Low  
Limit setting (minus the Low Limit Differential) and  
has not gone above the Low Limit setting; or, ZR  
input is powered with 120 Vac (only L7248L with  
ELL set On).  
bT  
Boiler Temperature  
HL  
HdF  
LL  
High Limit 1  
  
High Limit Differential  
  
4
.
Error: The controller has detected an error condition  
(e.g., open sensor) and has shut down the burner  
output. The ZC output is energized. The controller  
continues to monitor the system and automatically  
restarts if the error condition clears. Refer toTable 4.  
Low Limit (L7224 only)  
Ldf  
tt  
Low Limit Differential (L7224 only)  
Local Thermostat Status  
