Installation  
p
Turn off power to the heating system at the main electrical panel  
to avoid electrical shock. The installation should be carried out  
by an electrician.  
n
This thermostat can be connected to an electric heater to control the  
room temperature.  
High voltage thermostats must be installed onto an electrical  
box.  
For a new installation, choose a location about 5 ft. above the  
floor and on an inside wall.  
The thermostat must be installed on an inside wall facing the  
heating system.  
Avoid locations where there are air drafts (top of staircase, air  
outlet), dead air spots (behind a door), direct sunlight or con-  
cealed chimneys or stove pipes.  
Appearswhen  
the setpoint is  
displayed  
Temperature  
display  
Temperature  
adjustment buttons  
Heating indicator *  
Backlight button  
n Connect the power base wires to the power supply and load  
Set the switch to  
Off to cut power to  
the heater  
using solderless connectors for copper wires.  
Power  
*
The thermostat indicates how much heating is required to maintain the desired  
temperature. For example,  
is displayed when heating is at 40 percent.  
1 to 24% 25 to 49% 50 to 74% 75 to 99% 100%  
Display  
%
of heating  
2
.
Configuration  
The configuration switches are located at the back of the control  
module (faceplate).  
o
Load  
o If you wish to use a remote controller such as the CT240 or  
CT241 from Aube, insert the cable (use 18 to 22 gauge flexible  
wires) into one of the two holes available below the terminal  
board and connect to terminals 1 and 2 of the base.  
2
.1 Temperature Display (S1)  
The S1 switch allows you to select  
between °C and °F.  
p If you use an external sensor, insert the sensor wires through  
one of the two holes below the terminals (figure 2) and connect  
the wires to terminals 3 and 4 (no polarity).  
2
.2 Model (S2)  
The S2 switch allows you to control  
the temperature using either the  
thermostat’s built-in sensor or an  
external sensor.  
q Push the excess length of the high-voltage wires back into the  
electrical box.  
r Secure the power base to the electrical box using the provided  
screws.  
AF: Use built-in sensor (external sensor not required)  
s If necessary, set the configuration switches on the control mod-  
ule (refer to the control module user guide).  
F:  
Use external sensor (option)  
0
8162 / TH114-A-240D / TL7235  
69-2022  
1/11/06  
1/2  
Non-programmable Thermostat - Installation and User Guide  
href="
9
.
t Install the control module onto the base.  
u Apply power to heating system.  
Warranty  
;
Honeywell warrants this product, excluding battery, to be free from  
defects in the workmanship or materials, under normal use and ser-  
vice, for a period of one (1) year from the date of purchase by the  
consumer. If at any time during the warranty period the product is  
determined to be defective or malfunctions, Honeywell shall repair or  
replace it (at Honeywell's option).  
NOTE: Always keep the thermostat's vents clean and unobstructed.  
4
.
Power-up  
q
As soon as the thermostat is powered, it undergoes a  
series of tests before displaying the actual temperature.  
If the product is defective,  
(i) return it, with a bill of sale or other dated proof of purchase, to  
the place from which you purchased it, or  
5
.
Error Messages  
(
ii) call Honeywell Customer Care at 1-800-468-1502. Customer  
Care will make the determination whether the product should be  
returned to the following address: Honeywell Return Goods,  
Dock 4 MN10-3860, 1885 Douglas Dr N, Golden Valley, MN  
r
LO: The measured temperature is below the display  
range. Heating is activated.  
55422, or whether a replacement product can be sent to you.  
This warranty does not cover removal or reinstallation costs. This  
warranty shall not apply if it is shown by Honeywell that the defect or  
malfunction was caused by damage which occurred while the prod-  
uct was in the possession of a consumer.  
HI: The measured temperature is above the display  
range.  
6
.
Backlight  
Honeywell's sole responsibility shall be to repair or replace the prod-  
uct within the terms stated above. HONEYWELL SHALL NOT BE  
LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING  
ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING,  
DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WAR-  
RANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF  
THIS PRODUCT. Some states do not allow the exclusion or limitation  
of incidental or consequential damages, so this limitation may not  
apply to you.  
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY HONEY-  
WELL MAKES ON THIS PRODUCT. THE DURATION OF ANY  
IMPLIED WARRANTIES, INCLUDING THE WARRANTIES OF  
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PUR-  
POSE, IS HEREBY LIMITED TO THE ONE-YEAR DURATION OF  
THIS WARRANTY. Some states do not allow limitations on how long  
an implied warranty lasts, so the above limitation may not apply to  
you.  
s
The display illuminates for 5 seconds when the backlight button is  
pressed. When either of the  
minates for 10 seconds.  
buttons is pressed, the display illu-  
7
.
Temperature Setting  
The thermostat normally displays the actual temperature. To view the  
setpoint, press one of the buttons once. The setpoint will appear  
for 5 seconds. To change the setpoint, press one of the buttons  
until the desired temperature is displayed. To scroll the setpoint  
faster, do not release the button.  
t
8
.
Technical Specifications  
Power supply: 208/240 VAC, 50/60 Hz  
u
This warranty gives you specific legal rights, and you may have other  
rights which vary from state to state.  
If you have any questions concerning this warranty, please write Hon-  
eywell Customer Relations, 1985 Douglas Dr, Golden Valley, MN  
Maximum load:16 A (resistive only)  
3
3
328 W @ 208 VAC  
840 W @ 240 VAC  
Setpoint range: 40 °F - 86 °F (5 °C to 30 °C)  
Display range: 32 °F - 122 °F (0 °C - 50 °C)  
Display resolution: 1 °F (0.5 °C)  
55422 or call 1-800-468-1502. In Canada, write Retail Products  
ON15-02H, Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive,  
Scarborough, Ontario M1V4Z9.  
Heating cycle length: 15 minutes  
1
0.  
Storage: -4 °F to 120 °F (-20 °C to 50 °C)  
Remote controller input (ECONO): requires a dry contact  
Certifications: CSA/UL  
Customer Assistance  
If you have any questions about the operation of your thermostat,  
please go to http://yourhome.honeywell.com, or call Honeywell  
Customer Care toll-free at 1-800-468-1502.  
0
8162 / TH114-A-240D / TL7235  
69-2022  
1/11/06  
2/2  
Non-programmable Thermostat - Installation and User Guide