Installation Guide
Installer setup
Follow the procedure below to configure the thermostat to match the installed
heating/coolingꢀsystem,ꢀandꢀcustomizeꢀfeatureꢀoperationꢀasꢀdesired.
Function
number
Setting
0
1
Done
Next
MCR29454
Press s or t to change settings.
Press NEXT to advance to the next function.
PressꢀDONEꢀtoꢀexitꢀandꢀsaveꢀsettings.
Toꢀbegin,ꢀpress and hold the s and FAN
buttons until the display changes.
Setup function
Settings & options (factory default in bold)
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
1
System type
0
1 heat/1 cool conventional
1
1 heat/1 cool heat pump (no aux. heat)
Heatꢀonlyꢀ—ꢀ2-wireꢀsystems,ꢀ3-wireꢀzoneꢀvalvesꢀ(Seriesꢀ20),ꢀandꢀ
normally open zone valves
2
ꢀ
3
4
5
6
7
8
9
1
ꢀ
Heatꢀonlyꢀwithꢀfan
Cool only
2 heat/1 cool heat pump (with aux. heat)
2 heat/2 cool conventional
2ꢀheat/1ꢀcoolꢀconventional
1 heat/2 cool conventional
2 heat/2 cool heat pump (no aux. heat) - TH6320U only
ꢀ
0ꢀ 3ꢀheat/2ꢀcoolꢀheatꢀpumpꢀ(withꢀaux.ꢀheat)ꢀ-ꢀTH6320U only
2
3
5
Changeover valve
0
1
Changeover valve (O/B terminal energized in cooling)
Changeover valve (O/B terminal energized in heating)
(
O/B terminal)
Fan control
0
1ꢀ
Gas or oil furnace — equipment controls fan in heating
Electricꢀfurnaceꢀ—ꢀthermostatꢀcontrolsꢀfanꢀinꢀheating
(
heating)
Stage 1 heat cycle
rate (CPH: cycles/hour)* 1
5
For gas or oil furnaces of less than 90% efficiency
For steam or gravity systems
3
9
ꢀ
Forꢀhotꢀwaterꢀsystemsꢀ&ꢀfurnaces of over 90% efficiency
For electric furnaces
6
7
Stage 2 heat cycle
rate/Auxiliary heat
cycle rate (CPH)*
5
1
3ꢀ
9
For gas or oil furnaces of less than 90% efficiency
For steam or gravity systems
Forꢀhotꢀwaterꢀsystemsꢀ&ꢀfurnaces of over 90% efficiency
For electric furnaces
Auxiliary heat cycle
rate (CPH)*
5
1
For gas or oil furnaces of less than 90% efficiency
For steam or gravity systems
3
9
ꢀ
Forꢀhotꢀwaterꢀsystemsꢀ&ꢀfurnaces of over 90% efficiency
For electric furnaces
Only TH6320U
for 3H/2C Heat Pumps
8
Emergency heat cycle
rate (CPH)*
9
1
For electric emergency heat
For steam or gravity systems
3
5
ꢀ
Forꢀhotꢀwaterꢀsystemsꢀ&ꢀfurnaces of over 90% efficiency
For gas or oil furnaces of less than 90% efficiency
*[Otherꢀcycleꢀrateꢀoptions:ꢀ2,ꢀ4,ꢀ6,ꢀ7,ꢀ8,ꢀ10,ꢀ11ꢀorꢀ12ꢀCPH]
6
9-1920EFS—01
6
Continued on next page