VisionPRO™ 8000 Touchscreen  
Programmable Thermostat  
PRODUCT DATA  
FEATURES  
Large, clear display with backlight shows the current  
and set temperature and time—even in the dark.  
Menu-driven programming make setup effortless.  
Beautiful ergonomic design is smart and sophisticated  
to match your customers’ lifestyle.  
Touchscreen interaction  
Real-time clock keeps time during power failures and  
automatically updates to daylight savings.  
"Saving Changes" notification lets you know when the  
schedule changes have been saved.  
Change/check reminders let you know when to service  
or replace filters or batteries.  
Various Hold options allow you to override the  
program schedule, as desired.  
Speedy same-schedule programming—no need to  
copy multiple days.  
APPLICATION  
Armchair programming allows you to remove the  
thermostat from the wall for programming.  
The VisionPRO 8000 Touchscreen Programmable Thermostat  
is an effortless, 7-Day programmable thermostat that provides  
universal system compatibility, precise comfort control and is  
easy-to-program.  
Programmable fan offers increased air quality when  
combined with a Honeywell whole-house air cleaner.  
The TH8110 Thermostats provide temperature control for gas,  
oil, electric and heat pumps for 1 heat, 1 cool systems.  
The TH8320 Thermostats provide temperature control for gas,  
oil, electric and heat pumps for up to 3 heat, 2 cool systems  
including dual fuel operation.  
The TH8321 Thermostats provide temperature control for gas,  
oil, electric and heat pumps for up to 3 heat, 2 cool systems  
including dual fuel operation plus dehumidification control.  
Contents  
Application/Features..........................................................1  
Specifications/Ordering Information ..................................2  
Installation .........................................................................4  
Wiring ................................................................................5  
Power the Thermostat.......................................................11  
Installer Setup ...................................................................15  
Installer System Test .........................................................20  
Operation...........................................................................21  
Programming.....................................................................23  
Troubleshooting.................................................................38  
®
©
U.S. Registered Trademark  
2011 Honeywell International Inc.  
6
8-0280-01  
All Rights Reserved  
href="
VisionPROTM 8000 Touchscreen Programmable Thermostat  
Shipping Temperature:  
TH8000 VisionPRO™ Thermostats: -30 °F to 150 °F  
SPECIFICATIONS  
(-34.4°C to 65.6°C).  
Thermostat Description:  
Operating Relative Humidity (Non-condensing):  
TH8000 VisionPRO Thermostats: 5% to 90%.  
C7089U: 5% to 95%.  
Feature  
Description  
Battery only  
Common wire only  
Powering methods  
C7189U: 5% to 95%.  
Common wire with battery backup  
Humidity Setting Range (TH8321 models only):  
Cooling: 40% to 80% RH.  
System types (up to  Gas, oil or electric heat with air  
3
heat/2 cool or up  
conditioning  
Humidity Display Range (TH8321 models only):  
to 1heat/1cool,  
depending on  
model)  
Warm air, hot water, high-efficiency  
furnaces, heat pumps, steam and  
gravity  
Heat only—includes power to open  
and power to close zone valves  
0% to 99%.  
Cycle Rates (at 50% Load):  
Heating: Selectable 1 - 12 cycles per hour.  
Cooling: Selectable 1 - 6 cycles per hour.  
(series 20) and normally-open zone  
valves  
Heat only with fan  
Cool only  
Finish:  
TH8000 VisionPRO™ Thermostats: Premier White® color.  
C7189U Wall Mount Remote Indoor Sensor: Premier White®  
color.  
750 mV heating systems  
Changeover  
Manual or Auto changeover selectable  
System setting  
Heat-Off-Cool-Auto (Em. Heat for heat  
pumps)  
Clock Accuracy: +/- 1 minute per month.  
Batteries:  
Fan setting  
Auto-On-Circ  
Three replaceable AAA alkaline batteries: Power thermostats  
when 24 Vac common is not used. Non-replaceable  
lithium battery with ten-year life under normal use to hold  
calendar and time settings. Alkaline batteries keep calen-  
dar and time after lithium battery is no longer functional.  
Electrical Ratings:  
Terminal  
W Heating  
W Heating  
Voltage (50/60 Hz) Running Current  
20 - 30 Vac  
750 mV dc  
.02 - 1.0A  
Resistance Characteristics of Remote Sensors:  
C7089U Outdoor Sensor: Negative temperature coefficient  
(NTC) means that resistance decreases as the  
100 mA dc  
(Powerpile)  
temperature increases. See Table 13 in the Operation  
section for sensor resistance characteristics.  
C7189U Remote Indoor Sensor: Negative temperature  
coefficient (NTC), means that resistance decreases as the  
temperature increases. See Table 14 in the Operation  
section for sensor resistance characteristics.  
Y Cooling  
G Fan  
20 - 30 Vac  
20 - 30 Vac  
.02 - 1.0A  
.02 - .60A  
Temperature Setting Range:  
Heating: 40°F to 90°F(4.5°C to 32°C).  
Cooling: 50°F to 99°F (10°C to 37°C).  
Cool Indication:  
TH8000 VisionPRO™ Touchscreen Thermostats show "Cool  
On" on the screen when Cool is activated.  
Operating Ambient Temperature:  
TH8000 VisionPRO™ Thermostats: 0°F to 120°F  
-18°C to 49°C).  
(
C7089U: -40°F to 120°F (-40°C to 49°C).  
C7189U: 45°F to 88°F (7.2°C to 32°C).  
Heat Indication:  
TH8000 VisionPRO™ Touchscreen Thermostats show “Heat  
On” on the screen when Heat is activated.  
ORDERING INFORMATION  
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the  
TRADELINE® Catalog or price sheets for complete ordering number.  
If you have additional questions, need further information, or would like to comment on our products or services, please write or  
phone:  
1
.
Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).  
Honeywell Customer Care  
2.  
1
985 Douglas Drive North  
Minneapolis, Minnesota 55422-4386  
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.  
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,  
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.  
68-0280—01  
2
href="
VisionPROTM 8000 Touchscreen Programmable Thermostat  
Auxiliary Heat Indication:  
TH8000 VisionPRO™ Touchscreen Thermostats show “Aux.  
Heat On” on the screen when Auxiliary Heat is activated.  
WALLPLATE  
-3/8 (86)  
3
Emergency Heat Indication:  
TH8000 VisionPRO™ Touchscreen Thermostats show “Heat  
On” on the screen when Emergency Heat is activated and  
the System mode is in the Em. Heat position.  
3-3/8 (86)  
Calibration:  
C7089U, C7189U and TH8000 VisionPRO™ Touchscreen  
Thermostats are factory-calibrated and require no field  
calibration.  
THERMOSTAT  
AND WALLPLATE  
-3/8 (35)  
Interstage Differential:  
TH8000 VisionPRO™ Touchscreen Thermostats operate with  
droopless control. Once the thermostat senses that  
THERMOSTAT  
(152)  
1
6
1st stage is running at 90% capacity, the thermostat  
energizes 2nd stage.  
Nomenclature:  
4
(
-9/16  
116)  
System  
Power and System  
Series  
Stages Application Changeover  
VisionPRO™ 11 - 1H/1C 0 - Standard U - Universal (Auto  
000 32 - 3H/2C 1 - Humidity changeover and/or  
8
M22421  
Touchscreen  
Sensor  
manual change-  
over) dual powered,  
system flexibility,  
schedule flexibility.  
Fig. 1. TH8000 Touchscreen Thermostat  
dimensions in in. (mm).  
Mounting Means:  
1
-1/2 (38)  
TH8000 VisionPRO™ Touchscreen Thermostat: Mounts  
directly on the wall in the living space using mounting  
screws and anchors provided. Fits a vertical or horizontal  
2
x 4 in. junction box.  
C7089U Outdoor Sensor: Mounts outside of living space with  
mounting clip and screws provided.  
C7189U Remote Indoor Sensor: Mounts directly on the wall  
using mounting screws and anchors provided. Fits a  
vertical 2 x 4 in. junction box.  
Cover Plate:  
M4488  
32003796-001 Cover Plate is used to cover marks left on the  
wall by the old thermostat.  
Fig. 2. C7089U Outdoor Sensor Mounting Clip  
dimensions in in. (mm).  
Dimensions:  
TH8000 Touchscreen Thermostat: see Fig. 1.  
C7089U Outdoor Sensor Mounting Clip: see Fig. 2.  
3
2003796-001 Cover Plate: see Fig. 3.  
7
3
-7/8 (200)  
-5/16 (84)  
C7189U Remote Indoor Sensor: see Fig. 4.  
5
-1/2  
140)  
(
3
-5/16  
84)  
(
M22139  
Fig. 3. 32003796-001 Cover Plate dimensions in in. (mm).  
3
68-0280—01  
href="
VisionPROTM 8000 Touchscreen Programmable Thermostat  
4
(
-5/8  
117)  
4-5/8  
(117)  
3
(
-1/4  
83)  
1
(
-1/8  
29)  
2
-3/4 (70)  
2-3/4 (70)  
M4465  
FRONT VIEW  
SIDE VIEW  
FRONT VIEW (COVER OFF)  
Fig. 4. C7189U Remote Indoor Sensor dimensions in in. (mm).  
Do not install the thermostat where it can be affected by:  
INSTALLATION  
Drafts or dead spots behind doors and in corners.  
Hot or cold air from ducts.  
Radiant heat from sun or appliances.  
Concealed pipes and chimneys.  
Unheated (uncooled) areas such as an outside wall behind  
the thermostat.  
When Installing this Product...  
1.  
Read these instructions carefully. Failure to follow the  
instructions can damage the product or cause a hazard-  
ous condition.  
2.  
3.  
4.  
Check the ratings given in the instructions to make sure  
the product is suitable for your application.  
Installer must be a trained, experienced service  
technician.  
After completing installation, use these instructions to  
check out the product operation.  
Installing Wallplate  
CAUTION  
Electrical Hazard.  
Can cause electrical shock or equipment damage.  
Disconnect power before wiring.  
Selecting Location  
Install the thermostat about 5 ft. (1.5m) above the floor in an  
area with good air circulation at average temperature. See  
Fig. 5.  
The thermostat can be mounted horizontally on the wall or on  
a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.  
1.  
2.  
3.  
Position and level the wallplate (for appearance only).  
Use a pencil to mark the mounting holes.  
Remove the wallplate from the wall and, if drywall, drill  
two 3/16-in. holes in the wall, as marked. For firmer  
material such as plaster, drill two 7/32-in. holes. Gently  
tap anchors (provided) into the drilled holes until flush  
with the wall.  
NO  
YES  
NO  
NO  
5 FEET  
[
1.5 METERS]  
M19925  
Fig. 5. Selecting thermostat location.  
68-0280—01  
4
href="
VisionPROTM 8000 Touchscreen Programmable Thermostat  
4
.
.
Position the wallplate over the holes, pulling wires  
through the wiring opening. See Fig. 6.  
Insert the mounting screws into the holes and tighten.  
5
Table 1. Selecting Terminal Identifications for  
System Type.  
WALL  
Wallplate  
Terminal  
Identifications  
Wiring  
Diagram  
Reference  
WIRES THROUGH WALL  
AND WIRE SLOT  
System Type  
Standard Heat/Cool  
Heat Only  
WALL ANCHORS (2)  
Conventional  
Conventional  
Conventional  
Conventional  
9, 10  
11  
Heat Only with Fan  
12  
Heat Only (Series 20)  
Power to open and  
power to close zone  
valves  
13  
MOUNTING  
HOLES  
MOUNTING  
SCREWS (2)  
Normally Open Zone  
Valves—Heat Only  
Conventional  
14  
M19916  
Cool Only  
Conventional  
Conventional  
15  
Fig. 6. Mounting wallplate.  
Standard Multistage up  
to 2 Heat/2 Cool  
16, 17  
WIRING (FIG. 9 - 21)  
Heat Pump with No  
Auxiliary Heat  
Heat Pump  
Heat Pump  
18, 19  
20, 21  
All wiring must comply with local electrical codes and  
ordinances.  
Heat Pump with  
Auxiliary Heat  
1
.
.
Select set of terminal identifications (Table 1) that  
corresponds with system type (conventional or heat  
pump in Fig. 7).  
Loosen the screws for the appropriate system type  
selected; see Table 1. See Table 2 for terminal  
designation descriptions. Insert wires in the terminal  
block under the loosened screw. See Fig. 8.  
Securely tighten each screw.  
2
3.  
4.  
5.  
Push excess wire back into the hole.  
Plug the hole with nonflammable insulation to prevent  
drafts from affecting the thermostat.  
6.  
See Fig. 9 through 21 for typical wiring hookups.  
M19917  
HEAT PUMP  
CONVENTIONAL  
Fig. 8. Inserting wires in terminal block.  
Y2  
L
Y2  
RC  
R
RC  
R
IMPORTANT  
Use 18 gauge thermostat wire.  
E
W
Y
O/B  
Y
AUX  
S1  
S2  
W2  
S1  
S2  
G
G
C
C
SCREW TERMINALS  
M19951  
Fig. 7. Selecting terminal identifications for  
system type.  
5
68-0280—01  
href="
VisionPROTM 8000 Touchscreen Programmable Thermostat  
Table 2. Terminal Designation Descriptions.  
Terminal  
CONVENTIONAL  
2
Y2  
RC  
R
1
Designation  
Description  
W
Y
G
C
R
C
Rc (see Note  
Power for cooling--connect to  
secondary side of cooling system  
transformer  
W2  
S1  
1)  
OPTIONAL  
S2  
2
4 VAC  
COMMON  
CONNECTION  
R (see Note 1) Power for heating--connect to  
secondary side of heating system  
transformer  
3
FAN  
RELAY  
OUTDOOR/INDOOR  
TEMPERATURE  
SENSOR  
COMPRESSOR  
CONTACTOR  
C (see Note 2) Common wire from secondary side of  
cooling system transformer  
HEAT RELAY  
W
Heat relay  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
Y
Compressor contactor  
Fan relay  
2
3
FACTORY INSTALLED JUMPER.  
G
Y2  
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE  
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.  
M19895  
Second stage cooling  
Second stage heat relay  
W2  
Fig. 9. Typical hookup of conventional single-stage heat  
and cool system with single transformer  
O/B (see Note  
Changeover valve for heat pump  
systems  
3)  
(1H/1C conventional).  
AUX  
E
Auxiliary heat relay for heat pump  
systems  
CONVENTIONAL  
RC  
Emergency heat relay for heat pump  
systems  
Y2  
2
1
R
L (see note 4)  
S1, S2  
Equipment monitor for heat pump  
systems  
W
Y
G
R
C
W2  
S1  
Optional outdoor or indoor remote  
sensor  
S2  
C
OPTIONAL  
24 VAC  
COMMON  
CONNECTION  
3
FAN  
NOTES:  
RELAY  
OUTDOOR/INDOOR  
TEMPERATURE  
SENSOR  
1.  
When used in a single-transformer system, leave  
metal jumper wire in place between Rc and R. If  
used on a two-transformer system, remove metal  
jumper wire between Rc and R.  
COMPRESSOR  
CONTACTOR  
1
C
R
HEAT RELAY  
2
.
.
Common wire is optional when thermostat is used  
with batteries.  
3
If thermostat is configured for a heat pump system  
in the Installer Setup, configure changeover valve  
for cool (O-factory setting) or heat (B).  
L terminal is an input (system monitor) when the  
System mode is in the Heat, Off, Cool or Auto  
position. L terminal is a 24 Vac output when  
System mode is Emergency Heat. Must connect  
the 24 Vac Common when using the L terminal.  
See LED Indication section for more details.  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
2
3
REMOVE FACTORY INSTALLED JUMPER.  
4.  
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE  
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.  
M19896  
Fig. 10. Typical hookup of conventional single-stage heat  
and cool system with two transformers  
(1H/1C conventional).  
68-0280—01  
6
href="
VisionPROTM 8000 Touchscreen Programmable Thermostat  
CONVENTIONAL  
2
CONVENTIONAL  
Y2  
RC  
R
Y2  
RC  
R
1
2
1
W
Y
G
C
R
C
W
Y
G
C
R
C
W2  
S1  
W2  
S1  
OPTIONAL  
S2  
S2  
2
4 VAC  
COMMON  
CONNECTION  
3
3
HEAT RELAY  
OUTDOOR/INDOOR  
TEMPERATURE  
SENSOR  
OUTDOOR/INDOOR  
TEMPERATURE  
SENSOR  
W
B
R
SERIES 20  
MOTOR OR  
VALVE  
TR TR  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
2
3
FACTORY INSTALLED JUMPER.  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE  
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.  
2
3
FACTORY INSTALLED JUMPER.  
M19897  
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE  
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.  
M19899  
Fig. 11. Typical hookup of heat-only system  
(1 H conventional).  
Fig. 13. Typical hookup of heat only power to open and  
power to close zone valve (Series 20) system.  
CONVENTIONAL  
RC  
CONVENTIONAL  
Y2  
2
1
R
Y2  
RC  
R
W
Y
G
R
C
2
1
W2  
S1  
W
Y
R
C
W2  
S1  
OPTIONAL  
S2  
C
2
4 VAC  
G
COMMON