VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
SPECIFICATIONS
Thermostat Description:
Finish:
®
®
VisionPRO IAQ Thermostats: Premier White color.
THM5421C1008: Premier White color.
C7189U1005 Wall Mount Remote Indoor Sensor: Premier
®
Feature
Description
Common wire only
®
Powering method
•
White color.
System types (up to • Gas, oil or electric heat with air
Clock Accuracy: +/- 1 minute per year.
4
heat/2 cool)
conditioning
•
Warm air, hot water, high-efficiency
furnaces, heat pumps, steam and
gravity
Heat only with fan
Cool only
Resistance Characteristics of Remote Sensors:
C7089U1006 Outdoor Sensor: Negative temperature coeffi-
cient (NTC) means that resistance decreases as the tem-
perature increases. See Table 12 in the Operation section
for sensor resistance characteristics.
C7189U1005 Remote Indoor Sensor: Negative temperature
coefficient (NTC), means that resistance decreases as the
temperature increases. See Table 13 in the Operation sec-
tion for sensor resistance characteristics.
•
•
Changeover
System setting
Fan setting
Manual or Auto changeover selectable
Heat-Off-Cool-Auto
Auto-On-Circ
Electrical Ratings:
Cool Indication:
VisionPRO IAQ Comfort Systems show “Cool On” on the
®
thermostat screen when Cool is activated.
Terminal
Voltage (50/60 Hz) Running Current
W1 Heating
20 - 30 Vac
.02 - 1.0A
.02 - 1.0A
.02 - 1.0A
.02 - 1.0A
.02 - 1.0A
.02 - 1.0A
Heat Indication:
VisionPRO IAQ Comfort Systems show “Heat On” on the
®
W2/Aux Heating 20 - 30 Vac
W3/Aux2 Heating 20 - 30 Vac
thermostat screen when Heat is activated.
Y Cooling
Y2 Cooling
G Fan
20 - 30 Vac
20 - 30 Vac
20 - 30 Vac
Auxiliary Heat Indication:
®
VisionPRO IAQ Comfort Systems show “Aux. Heat On” on
the thermostat screen when Auxiliary Heat is activated.
Calibration:
®
Temperature Setting Range:
C7089U1006, C7189U1005 and VisionPRO IAQ Comfort Sys-
Heating: 40°F to 90°F(4.5°C to 32°C).
Cooling: 50°F to 99°F (10°C to 37°C).
tems are factory-calibrated and require no field calibration.
Interstage Differential:
®
Operating Ambient Temperature:
VisionPRO IAQ Comfort Systems operate with droopless
VisionPRO® IAQ Thermostats: 0°F to 120°F
control. Once the thermostat senses that 1st stage is run-
(-18°C to 49°C).
ning at 90% capacity, the thermostat energizes 2nd stage.
THM5421C1008: -30°F to 150°F (-34°C to 66°C).
C7089U1006: -40°F to 120°F (-40°C to 49°C).
C7189U1005: 45°F to 88°F (7°C to 32°C).
Mounting Means:
VisionPRO IAQ Comfort System: Thermostat mounts directly
®
on the wall in the living space using mounting screws and
anchors provided. Fits a vertical or horizontal 2 x 4 in. junc-
tion box.
Shipping Temperature:
VisionPRO® IAQ Thermostats: -30°F to 150°F
(
-34°C to 66°C).
THM5421C1008 Equipment Interface Module (EIM) mounts on
HVAC equipment or on a wall in the equipment room.
C7089U1006 Outdoor Sensor: Mounts outside of living space
with mounting clip and screws provided.
THM5421C1008: -30°F to 150°F (-34°C to 66°C).
Operating Relative Humidity (Non-condensing):
VisionPRO® IAQ Thermostats: 5% to 90%.
THM5421C1008: 5% to 90%.
C7189U1005 Remote Indoor Sensor: Mounts directly on the
wall using mounting screws and anchors provided.
C7089U1006: 5% to 95%.
C7189U1005: 5% to 95%.
Cover Plate:
3
2003796-001 Cover Plate is used to cover marks left on the
wall by the old thermostat.
Humidification Setting Range:
Heating: 10% to 60% RH.
Dimensions:
VisionPRO IAQ Comfort System: see Fig. 1.
®
Dehumidification Setting Range:
Heating: 40% to 80% RH.
THM5421C1008: see Fig. 2
C7089U1006 Outdoor Sensor Mounting Clip: see Fig. 3.
Humidity Display Range:
32003796-001 Cover Plate: see Fig. 4.
C7189U1005 Remote Indoor Sensor: see Fig. 5.
0% to 99%.
Cycle Rates (at 50% Load):
Heating: Selectable 1 - 12 cycles per hour.
Cooling: Selectable 1 - 6 cycles per hour.
6
8-0287—1
2