VisionPRO IAQ  
Total Home Comfort System  
PRODUCT DATA  
FEATURES  
Large, clear display with backlight shows the current  
and set temperature and time—even in the dark.  
Touchscreen interaction  
Real-time clock keeps time during power failures and  
automatically updates to daylight savings.  
Change/check reminders let you know when to service  
or replace filters.  
Various Hold options allow you to override the  
program schedule, as desired.  
Controls humidification to increase homeowner  
comfort while protecting woodwork and furnishings.  
Controls dehumidification using air conditioner with  
high or low speed fan or a whole house dehumidifier.  
Controls ventilation with other HRV, ERV, or Freshair  
damper. Vent on demand and automatically using  
patented advanced ventilation control.  
Advanced heat pump control featuring balance point  
plus 2°F droop to increase homeowner comfort.  
APPLICATION  
®
The VisionPRO IAQ Total Home Comfort System features an  
effortless, 7-Day programmable touchscreen thermostat that  
provides control of temperature, humidification,  
dehumidification, and ventilation.  
Contents  
Application/Features..........................................................  
Specifications/Ordering Information ..................................  
Installation ........................................................................  
Wiring ...............................................................................  
Power the Thermostat ......................................................  
1
2
4
5
8
Installer Setup .................................................................. 12  
Operation .......................................................................... 19  
Programming .................................................................... 25  
Troubleshooting ................................................................ 35  
6
8-0287-1  
href="
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM  
SPECIFICATIONS  
Thermostat Description:  
Finish:  
®
®
VisionPRO IAQ Thermostats: Premier White color.  
THM5421C1008: Premier White color.  
C7189U1005 Wall Mount Remote Indoor Sensor: Premier  
®
Feature  
Description  
Common wire only  
®
Powering method  
White color.  
System types (up to  Gas, oil or electric heat with air  
Clock Accuracy: +/- 1 minute per year.  
4
heat/2 cool)  
conditioning  
Warm air, hot water, high-efficiency  
furnaces, heat pumps, steam and  
gravity  
Heat only with fan  
Cool only  
Resistance Characteristics of Remote Sensors:  
C7089U1006 Outdoor Sensor: Negative temperature coeffi-  
cient (NTC) means that resistance decreases as the tem-  
perature increases. See Table 12 in the Operation section  
for sensor resistance characteristics.  
C7189U1005 Remote Indoor Sensor: Negative temperature  
coefficient (NTC), means that resistance decreases as the  
temperature increases. See Table 13 in the Operation sec-  
tion for sensor resistance characteristics.  
Changeover  
System setting  
Fan setting  
Manual or Auto changeover selectable  
Heat-Off-Cool-Auto  
Auto-On-Circ  
Electrical Ratings:  
Cool Indication:  
VisionPRO IAQ Comfort Systems show “Cool On” on the  
®
thermostat screen when Cool is activated.  
Terminal  
Voltage (50/60 Hz) Running Current  
W1 Heating  
20 - 30 Vac  
.02 - 1.0A  
.02 - 1.0A  
.02 - 1.0A  
.02 - 1.0A  
.02 - 1.0A  
.02 - 1.0A  
Heat Indication:  
VisionPRO IAQ Comfort Systems show “Heat On” on the  
®
W2/Aux Heating 20 - 30 Vac  
W3/Aux2 Heating 20 - 30 Vac  
thermostat screen when Heat is activated.  
Y Cooling  
Y2 Cooling  
G Fan  
20 - 30 Vac  
20 - 30 Vac  
20 - 30 Vac  
Auxiliary Heat Indication:  
®
VisionPRO IAQ Comfort Systems show “Aux. Heat On” on  
the thermostat screen when Auxiliary Heat is activated.  
Calibration:  
®
Temperature Setting Range:  
C7089U1006, C7189U1005 and VisionPRO IAQ Comfort Sys-  
Heating: 40°F to 90°F(4.5°C to 32°C).  
Cooling: 50°F to 99°F (10°C to 37°C).  
tems are factory-calibrated and require no field calibration.  
Interstage Differential:  
®
Operating Ambient Temperature:  
VisionPRO IAQ Comfort Systems operate with droopless  
VisionPRO® IAQ Thermostats: 0°F to 120°F  
control. Once the thermostat senses that 1st stage is run-  
(-18°C to 49°C).  
ning at 90% capacity, the thermostat energizes 2nd stage.  
THM5421C1008: -30°F to 150°F (-34°C to 66°C).  
C7089U1006: -40°F to 120°F (-40°C to 49°C).  
C7189U1005: 45°F to 88°F (7°C to 32°C).  
Mounting Means:  
VisionPRO IAQ Comfort System: Thermostat mounts directly  
®
on the wall in the living space using mounting screws and  
anchors provided. Fits a vertical or horizontal 2 x 4 in. junc-  
tion box.  
Shipping Temperature:  
VisionPRO® IAQ Thermostats: -30°F to 150°F  
(
-34°C to 66°C).  
THM5421C1008 Equipment Interface Module (EIM) mounts on  
HVAC equipment or on a wall in the equipment room.  
C7089U1006 Outdoor Sensor: Mounts outside of living space  
with mounting clip and screws provided.  
THM5421C1008: -30°F to 150°F (-34°C to 66°C).  
Operating Relative Humidity (Non-condensing):  
VisionPRO® IAQ Thermostats: 5% to 90%.  
THM5421C1008: 5% to 90%.  
C7189U1005 Remote Indoor Sensor: Mounts directly on the  
wall using mounting screws and anchors provided.  
C7089U1006: 5% to 95%.  
C7189U1005: 5% to 95%.  
Cover Plate:  
3
2003796-001 Cover Plate is used to cover marks left on the  
wall by the old thermostat.  
Humidification Setting Range:  
Heating: 10% to 60% RH.  
Dimensions:  
VisionPRO IAQ Comfort System: see Fig. 1.  
®
Dehumidification Setting Range:  
Heating: 40% to 80% RH.  
THM5421C1008: see Fig. 2  
C7089U1006 Outdoor Sensor Mounting Clip: see Fig. 3.  
Humidity Display Range:  
32003796-001 Cover Plate: see Fig. 4.  
C7189U1005 Remote Indoor Sensor: see Fig. 5.  
0% to 99%.  
Cycle Rates (at 50% Load):  
Heating: Selectable 1 - 12 cycles per hour.  
Cooling: Selectable 1 - 6 cycles per hour.  
6
8-0287—1  
2
href="
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM  
WALLPLATE  
-3/8 (86)  
1-1/2 (38)  
3
3
-3/8 (86)  
M4488  
THERMOSTAT  
AND WALLPLATE  
-3/8 (35)  
Fig. 3. C7089U1006 Outdoor Sensor Mounting Clip  
dimensions in in. (mm).  
THERMOSTAT  
(152)  
1
6
7
3
-7/8 (200)  
-5/16 (84)  
4-9/16  
(116)  
5
-1/2  
140)  
(
3
-5/16  
84)  
(
M23539  
Fig. 1. VisionPRO® IAQ Comfort System  
dimensions in in. (mm).  
M22139  
Fig. 4. 32003796-001 Cover Plate dimensions in in. (mm).  
7-9/32  
(185)  
6
-57/64  
175)  
(
4
-35/64  
116)  
1-21/64  
(34)  
(
FRONT VIEW  
SIDE VIEW  
M23544  
Fig. 2. THM5421C1008 Equipment Interface Module  
dimensions in in. (mm).  
3
68-0287—1  
href="
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM  
2
-9/32  
58)  
2-9/32  
(58)  
(
1
-1/2 (38)  
45/64  
18)  
1-1/2 (38)  
(
M23522  
FRONT VIEW  
SIDE VIEW  
FRONT VIEW (COVER OFF)  
Fig. 5. C7189U1005 Remote Indoor Sensor dimensions in in. (mm).  
Do not install the thermostat where it can be affected by:  
INSTALLATION  
Drafts or dead spots behind doors and in corners.  
Hot or cold air from ducts.  
Radiant heat from sun or appliances.  
Concealed pipes and chimneys.  
Unheated (uncooled) areas such as an outside wall behind  
the thermostat.  
When Installing this Product...  
1.  
Read these instructions carefully. Failure to follow the  
instructions can damage the product or cause a hazard-  
ous condition.  
2.  
3.  
4.  
Check the ratings given in the instructions to make sure  
the product is suitable for your application.  
Installer must be a trained, experienced service  
technician.  
After completing installation, use these instructions to  
verify the product operation.  
Installing Wallplate  
CAUTION  
Electrical Hazard.  
Can cause electrical shock or equipment damage.  
Disconnect power before wiring.  
Selecting Location  
Install the thermostat about 5 ft. (1.5m) above the floor in an area  
with good air circulation at average temperature. See Fig. 6.  
The thermostat can be mounted horizontally on the wall or on a  
in. x 2 in. (101.6 mm x 50.8 mm) wiring box.  
4
1.  
2.  
3.  
Position and level the wallplate (for appearance only).  
Use a pencil to mark the mounting holes.  
Remove the wallplate from the wall and, if drywall, drill  
two 3/16-in. holes in the wall, as marked. For firmer  
material such as plaster, drill two 7/32-in. holes. Gently  
tap anchors (provided) into the drilled holes until flush  
with the wall.  
NO  
YES  
NO  
NO  
5 FEET  
[
1.5 METERS]  
M19925  
Fig. 6. Selecting thermostat location.  
6
8-0287—1  
4
href="
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM  
4
.
.
Position the wallplate over the holes, pulling wires  
through the wiring opening. See Fig. 7.  
Insert the mounting screws into the holes and tighten.  
NOTE: It is normal for the LED to blink continuously during  
startup, and while checking equipment status (Auto  
Discover mode).  
5
WALL  
WIRES THROUGH WALL  
AND WIRE SLOT  
WALL ANCHORS (2)  
WALL ANCHOR  
COMMUNICATION LED  
MOUNTING  
HOLES  
DRILL 3/16 IN. HOLES  
FOR DRYWALL. DRILL  
M23541  
7
/32 IN. HOLES FOR  
PLASTER  
MOUNTING  
SCREWS (2)  
M23543  
Fig. 7. Mounting wallplate.  
Installing Equipment Interface Module (EIM)  
MOUNTING SCREW  
M23484  
CAUTION  
Electrical Hazard.  
Fig. 8. Mounting EIM.  
Can cause electrical shock or equipment damage.  
Disconnect power before wiring.  
WIRING  
The EIM can be mounted vertically on the HVAC equipment or  
on a wall in the equipment room.  
All wiring must comply with local electrical codes and  
ordinances. See Fig. 10–20.  
1.  
2.  
3.  
Position the EIM.  
Use a pencil to mark the mounting holes.  
Remove the wallplate from the wall and, if drywall, drill  
two 3/16-in. holes in the wall, as marked. For firmer  
material such as plaster, drill two 7/32-in. holes. Gently  
tap anchors (provided) into the drilled holes until flush  
with the wall.  
1
.
.
Select set of terminal identifications (Table 1) that corre-  
sponds with system type.  
Loosen the screws for the appropriate system type  
selected; see Table 1. See Table 2 for terminal designa-  
tion descriptions. Insert wires in the terminal block under  
the loosened screw. See Fig. 9.  
2
4
.
.
Position the wallplate over the holes, pulling wires  
through the wiring opening.  
Insert the mounting screws into the holes and tighten.  
See Fig. 8.  
3.  
4.  
5.  
Securely tighten each screw.  
Push excess wire back into the hole.  
Plug the hole with nonflammable insulation to prevent  
drafts from affecting the thermostat.  
5
6.  
See Fig. 10–20 for typical wiring hookups.  
Communication LED  
The EIM has an LED (see Fig. 8) that communicates the EIM  
status as follows.  
Table 1. Selecting Terminal Identifications for System Type.  
Wallplate Terminal Wiring Diagram  
LED blinks rapidly: Normal information transfer.  
LED blinks once: Incoming message to EIM.  
LED blinks continuously: Wiring problem. Check wiring to  
terminals 1, 2, 3.  
System Type  
Identifications  
Reference  
10, 11  
12  
Standard Heat/Cool Conventional  
StandardMultistage Conventional  
up to 3 Heat/2 Cool  
LED always off: Wiring problem. Check wiring to terminals  
1
, 2, 3.  
Heat Pump with  
Auxiliary Heat  
Heat Pump  
13  
LED always on: EIM may need replacement.  
5
68-0287—1  
href="
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM  
NOTES:  
1.  
When used in a single-transformer system, leave  
the metal jumper wires in place between R and Rc,  
and Rc and Rh. If used on a two-transformer sys-  
tem, remove metal jumper wire between Rc and Rh.  
If thermostat is configured for a heat pump system  
in the Installer Setup, configure changeover valve  
for cool (O-factory setting) or heat (B).  
2.  
For wiring to a W8835 Zone panel please refer to the product  
data sheet included with the panel.  
M23541  
Fig. 9. Inserting wires in terminal block.  
1
IMPORTANT  
COMMUNICATION LED  
COMMUNICATION  
TERMINALS  
Use 18-gauge thermostat wire.  
1
2
3
1
CONV. HP  
W1 O/B  
2
3
Table 2. Terminal Designation Descriptions.  
W2 AUX  
C
2
4 VAC  
W3 AUX2  
R
THM5421C1008  
Terminal  
Designations  
Y
Y
RC  
RH  
Y2 Y2  
Function  
G
G
1
2
3
Terminal 1—data to/from thermostat  
Terminal 2—power from thermostat (24Vac)  
Terminal 3—common from thermostat  
FACTORY INSTALLED  
JUMPER BETWEEN R,  
RC AND RH  
1
WIRE TO TERMINALS ON THERMOSTAT.  
M23485  
(24Vac)  
Fig. 10. Typical hookup of conventional single-stage heat  
and cool system with single transformer  
C
24 Vac Transformer Common  
24 Vac Transformer  
R
(
1H/1C conventional).  
RC  
24 Vac Cooling Transformer  
24 Vac Heating Transformer  
Humidification Connection (normally open)  
RH  
1
HUM1/HUM2  
DHM1/DHM2  
1
COMMUNICATION LED  
1
COMMUNICATION  
TERMINALS  
CONV. HP  
W1 O/B  
2
3
2
Dehumidification Connection (normally  
open or closed based on installer setup)  
3
W2 AUX  
C
2
4 VAC  
W3  
Y
AUX2  
Y
VNT1/VNT2  
W1/O/B  
Ventilation connection (normally open)  
R
Stage 1 Heating Relay (Conventional)  
Change-over Relay (Heat Pump)  
RC  
RH  
Y2 Y2  
G
G
W2/AUX  
Stage 2 Heating Relay (Conventional)  
Auxiliary Heat (fossil fuel or electric) (Heat  
Pump)  
OIL PRIMARY/  
AQUASTAT  
FACTORY INSTALLED JUMPER BETWEEN R,  
AND RC (REMOVE FACTORY INSTALLED  
JUMPER BETWEEN RC AND RH  
W3/AUX2  
Stage 3 Heating Relay (Conventional)  
Auxiliary Heat (fossil fuel or electric) (Heat  
Pump)  
1
WIRE TO TERMINALS ON THERMOSTAT.  
M23486  
Fig. 11. Typical hookup of conventional single-stage heat  
and cool system with oil primary (1H/1C conventional).  
Y
Stage 1 Compressor Relay  
Stage 2 Compressor Relay  
Fan Relay  
Y2  
G
L
Heat Pump Equipment Monitor  
Outdoor Temperature Sensor  
Remote Indoor Temperature Sensor  
OUT1/OUT2  
IN1/IN2  
DATS1/DATS2 Discharge Air Temperature Sensor  
6
8-0287—1  
6
href="
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM  
KEY  
1
2
3
C
=
=
NORMALLY OPEN, DRY CONTACTS  
2
4 VAC  
R
RC  
RH  
NORMALLY CLOSED, DRY CONTACTS  
M23685  
H1  
U
POWERED  
HUMIDIFIER  
M2  
D1  
H
OR  
1
M2  
HEAT 1 RELAY  
COMMUNICATION LED  
V1  
N
1
2
3
1
COMMUNICATION CONV. HP  
T2  
2
TERMINALS  
W1 O/B  
HEAT 2 RELAY  
HEAT 3 RELAY  
COOL 1 RELAY  
COOL 2 RELAY  
FAN RELAY  
M23490  
3
W2 AUX  
C
2
4 VAC  
W3 AUX2  
Fig. 15. Typical hookup of powered humidifier.  
R
Y
Y
RC  
RH  
Y2 Y2  
G
G
1
2
3
C
FACTORY INSTALLED  
JUMPER BETWEEN R,  
RC AND RH  
2
4 VAC  
1
WIRE TO TERMINALS ON THERMOSTAT.  
M23487  
R
RC  
RH  
Fig. 12. Typical hookup of conventional system with up to  
three-stage heat and two-stage cool with one transformer  
FIELD INSTALLED  
JUMPER BETWEEN  
R AND DHM 1  
(
3H/2C, 2H/2C, 2H/1C, 1H/2C, 1H/1C conventional).  
H1  
U
M2  
D1  
H
OR  
LOW SPEED  
FAN  
M2  
1
CHANGEOVER  
V1  
N
COMMUNICATION LED  
1
2
3
1
T2  
COMMUNICATION CONV. HP  
2
TERMINALS  
W1 O/B  
AUX 1 (HEAT 3)  
AUX 2 (HEAT 4)  
COMP 1  
M23491  
3
W2 AUX  
C
Fig. 16. Typical hookup of variable speed blower for  
dehumidification in low speed (contacts normally closed).  
2
4 VAC  
W3 AUX2  
R
Y
Y
RC  
RH  
Y2 Y2  
COMP 2  
NOTE: Connect DHM2 to low-speed fan terminal on air han-  
dler for dehumidification with air conditioner and a  
low-speed fan.  
G
G
FAN RELAY  
FACTORY INSTALLED  
JUMPER BETWEEN R,  
RC AND RH  
1
WIRE TO TERMINALS ON THERMOSTAT.  
M23488  
1
2
3
C
Fig. 13. Typical hookup of heat pump system  
(up to 4H/2C heat pump).  
2
4 VAC  
R
RC  
RH  
1
2
3
H1  
U
C
R
RC  
M2