Français : voir la page 17 • Español: vea la página 33
System-specific wiring guides
Humidification systems
See [notes] below.
Steam humidifier (or any humidifier with
its own transformer) [3, 4]
Bypass, flow-through humidifier (or
any humidifier that uses the system
transformer) [3]
Rc
R
Power [1]
[R+Rc joined by jumper] [2]
Rc
R
Power [1]
[R+Rc joined by jumper] [2]
HUM1Humidifier relay [5]
HUM2Humidifier relay [5]
HUM1Field jumper R to HUM 1 [5]
HUM2Humidifier relay [5]
Dehumidification systems
See [notes] below.
A/C with low-speed fan [7]
Whole house dehumidifier [6]
Rc
R
Power [1]
[R+Rc joined by jumper] [2]
Rc
R
Power [1]
[R+Rc joined by jumper] [2]
DHM1Dehumidifier relay [5]
DHM2Dehumidifier relay [5]
DHM1Field jumper Rc to DHM 1 [8]
DHM2Dehumidifier relay [8, 9]
[
[
1] Power supply. Provide disconnect means and overload protection as required.
2] Remove jumper (R to Rc) for systems with two transformers. Common connection
must come from cooling transformer.
[3] If using a humidifier that is wired directly to the thermostat, set humidification control
to Wired in Installer Setup.
[
4] If using a wireless adapter (THM4000R) with a TrueSTEAM humidifier, set humidification
control to Wireless in Installer Setup. Connect nothing to thermostat HUM terminals.
5] Terminals are normally open dry contacts.
[
[
[
[
[
6] In Installer Setup, set dehumidification setting to Whole House Dehumidifier.
7] In Installer Setup, set dehumidification setting to Dehumidify with Air Conditioner.
8] Terminals are normally closed dry contacts.
9] Equipment must include dehumidification terminal for low-speed fan.
7