Installation  
Operation  
Maintenance  
Voyagerâ„¢ II Rooftop units  
Cooling onlyTKD/TKH 155 175 200 250  
Reversible WKD/WKH 125 155 200  
Gas-FiredYKD/YKH 155 175 200 250  
R22 - R407C Refrigerant  
RT-SVX19A-E4  
href="
General information  
Foreword  
Warnings and cautions  
Reception  
These instructions are given as a  
guide to good practice in the  
installation, start-up, operation, and  
maintenance by the user, ofTrane  
TKD/TKH, WKD/WKH andYKD/YKH  
units.They do not contain full  
service procedures necessary for  
the continued successful operation  
of this equipment.The services of a  
qualified technician should be  
employed through the medium of a  
maintenance contract with a  
Warnings and Cautions appear at  
appropriate sections throughout  
this manual.Your personal safety  
and the proper operation of this  
machine require that you follow  
them carefully.The constructor  
assumes no liability for installations  
or servicing performed by  
On arrival, inspect the unit before  
signing the delivery note.  
In case of visible damage:The  
consignee (or the site  
representative) must specify any  
damage on the delivery note,  
legibly sign and date the delivery  
note, and the truck driver must  
countersign it.The consignee (or the  
site representative) must notify  
Trane Epinal Operations - Claims  
team and send a copy of the  
delivery note.The customer (or the  
site representative) should send a  
registered letter to the last carrier  
within 3 days of delivery.  
unqualified personnel.  
WARNING! : Indicates a potentially  
hazardous situation which, if not  
avoided, could result in death or  
serious injury.  
reputable service company. Read  
this manual thoroughly before unit  
start-up.  
CAUTION! : Indicates a potentially  
hazardous situation which, if not  
avoided, may result in minor or  
moderate injury. It may also be  
used to alert against unsafe  
TKD/TKH units are designed to  
operate in cooling mode only, with  
optional auxiliary heat (electric  
heater or hot water coil).  
Reception in France only:  
practices or for equipment or  
property-damage-only accidents.  
Concealed damage must be looked  
for at delivery and immediately  
treated as visible damage.  
WKD/WKH can operate in cooling  
mode or heating mode by reversing  
the refrigeration cycle with or  
without auxiliary heat.  
Safety recommendations  
Reception in all countries except  
France:  
To avoid death, injury, equipment or  
property damage, the following  
recommendations should be  
observed during maintenance and  
service visits:  
1. The maximum allowable  
pressures for system leak testing  
on low and high pressure side  
are given in the chapter  
YKD/YKH units are designed to  
operate In cooling mode and  
equipped with a gas fired heating  
module.  
In case of concealed damage:The  
consignee (or the site  
representative) must send a  
registered letter to the last carrier  
within 7 days of delivery, claiming  
for the described damage. A copy of  
this letter must be sent toTrane  
Epinal Operations - Claims team.  
TKD/TKH, WKD/WKH andYKD/YKH  
units are assembled, pressure  
tested, dehydrated, charged and run  
tested before shipment.  
"Installation". Always provide a  
pressure regulator.  
2. Disconnect the main power  
supply before any servicing on  
the unit.  
3. Service work on the refrigeration  
system and the electrical system  
should be carried out only by  
qualified and experienced  
personnel.  
2
RT-SVX19A-E4  
href="
General information  
Warranty  
Refrigerant  
Storage  
Warranty is based on the general  
terms and conditions of the  
manufacturer.The warranty is void if  
the equipment is repaired or  
The refrigerant provided by the  
manufacturer meets all the  
Take precautions to prevent  
condensate formation inside the  
unit's electrical components and  
motors when:  
1. The unit is stored before it is  
installed; or,  
2. The unit is set on the roof curb  
and temporary auxiliary heat is  
provided in the building.  
requirements of our units. When  
using recycled or reprocessed  
refrigerant, it is advisable to ensure  
its quality is equivalent to that of a  
new refrigerant. For this, it is  
necessary to have a precise analysis  
made by a specialized laboratory. If  
this condition is not respected, the  
manufacturer warranty could be  
cancelled.  
modified without the written  
approval of the manufacturer, if the  
operating limits are exceeded or if  
the control system or the electrical  
wiring is modified. Damage due to  
misuse, lack of maintenance or  
failure to comply with the  
manufacturer's instructions or  
recommendations is not covered by  
the warranty obligation. If the user  
does not conform to the rules of  
this manual, it may entail  
Isolate all side panel service  
entrances and base pan openings  
(e.g., conduit holes, S/A and R/A  
openings, and flue openings) to  
minimize ambient air from entering  
the unit until it is ready for start-up.  
Maintenance contract  
It is strongly recommended that you  
sign a maintenance contract with  
your local Service Agency.This  
contract provides regular  
maintenance of your installation by  
a specialist in our equipment.  
Regular maintenance ensures that  
any malfunction is detected and  
corrected in good time and  
minimizes the possibility that  
serious damage will occur. Finally,  
regular maintenance ensures the  
maximum operating life of your  
equipment. We would remind you  
that failure to respect these  
installation and maintenance  
instructions may result in  
cancellation of warranty and  
liabilities by the manufacturer.  
Do not use the unit's heater as  
temporary heat without completing  
the start-up procedures detailed  
under "Unit Start-Up".  
TheTrane Company will not assume  
responsibility for equipment  
damage resulting from  
accumulation of condensate on the  
unit electrical components.  
Training  
To assist you in obtaining the best  
use of it and maintaining it in  
perfect operating condition over a  
long period of time, the  
manufacturer has at your disposal a  
refrigeration and air conditioning  
service school.The principal aim of  
this is to give operators and  
immediate cancellation of the  
warranty.  
technicians a better knowledge of  
the equipment they are using, or  
that is under their charge. Emphasis  
is particularly given to the  
importance of periodic checks on  
the unit operating parameters as  
well as on preventive maintenance,  
which reduces the cost of owning  
the unit by avoiding serious and  
costly breakdown.  
RT-SVX19A-E4  
3
href="
Contents  
Foreword  
2
2
2
2
3
3
3
3
3
Warnings and Cautions  
Safety recommendations  
Reception  
Warranty  
Refrigerant  
Maintenance contract  
Storage  
Training  
Installation  
6
Reception of units  
6
Roof curb installation  
7
Dimensions/Weights/Clearances  
Installing the unit  
8
10  
12  
13  
14  
15  
17  
20  
26  
Condensate drain piping  
Gas pipework installation  
Filter installation  
Supply fan adjustment  
Component air pressure drops  
Supply fan performances  
Electrical connection  
Controls  
31  
Control wiring  
31  
33  
36  
37  
38  
38  
38  
38  
38  
39  
CO sensors  
2
Remote potentiometer  
Fire thermostat  
Clogged filter detector  
Smoke detector  
High temperature safety thermostat  
Remote fault relay  
Thermostats  
Communication Interfaces  
4
RT-SVX19A-E4  
href="
Contents  
Unit Options  
40  
Hot water coil  
40  
41  
41  
42  
43  
Electric Heater  
Soft Starter  
0 - 25% fresh air hood  
Barometric relief  
Operation  
44  
Operation with a conventional thermostat  
Setting the economizer  
Test procedures  
44  
47  
49  
50  
51  
54  
55  
55  
56  
56  
56  
57  
Test modes  
Unit start-up  
Cooling without an Economizer  
Low Ambient Operation  
Cooling with an Economizer  
Economizer Set-Up  
ReliaTelâ„¢ Control Heating Operation  
Ignition Module  
Final installation checklist  
Maintenance  
58  
End user routine maintenance  
Service technician maintenance  
Troubleshooting  
58  
59  
60  
RT-SVX19A-E4  
5
href="
Installation  
General information :The  
installation must conform to all  
local standards and regulations.  
There are two ways to handle the  
unit:  
1. Use the openings in the wooden  
frame to handle the machine  
using a fork lift, in accordance  
with applicable safety  
Reception of units  
Rooftop unit  
regulations.  
The unit is supplied on a wooden  
frame. It is recommended to check  
the machine's condition upon  
reception.  
2. Use a lifting beam correctly  
adjusted to fit the unit  
(Figure 1a).  
Unit handling  
The units are supplied on the truck  
but are not unloaded. An opening is  
provided on each corner of the unit  
base to facilitate handling.  
4 shackles and 4 slings are required.  
Use a lifting beam to prevent the  
cables pressing too hard on top of  
the unit during lifting.  
Figure 1a indicates the position of  
the center of gravity and the lifting  
recommendations.  
Important: For unit to fit on the  
roof curb the fork lift pockets must  
be removed.  
Figure 1a - Unit handling  
B
A
1 = Clevis  
2 = Base Rail  
3 = Spreader Bar  
L = Length (Center of Gravity)  
W = Width (Center of Gravity)  
Refer toTable 2 for weights and center of gravity.  
6
RT-SVX19A-E4  
href="
Installation  
Table 1 - Sling lengths and maximum unit weight  
Roof curb Installation  
(TKD-WKD-YKD  
accessories)  
Maximm weight  
Unit size  
A (mm)  
B (mm)  
kg  
125  
155  
175  
400  
500  
3000  
3000  
3000  
3500  
3500  
1900  
1900  
1900  
2200  
2200  
644  
773  
Roof curbs are available as an  
accessory for "downflow" units to  
support the unit and ensure the  
water tightness between the rooftop  
and the roof.Two types of roof  
curbs are available:The standard  
version to allow the installation of  
the unit on a flat roof and the  
adjustable version for a sloped roof  
installation. (See Figure 1b for the  
maximum slope correction of  
adjustable roofcurb.)  
810  
1001  
1027  
Figure 1b - Maximum slope correction of adjustable roof curb.  
The adjustable roof curbs are  
supplied pre-assembled on a skid.  
Two types of self-adhesive seals are  
provided separately. (40 mm wide  
for the perimeter, 20 mm wide for  
the cross pieces). Make sure they  
are properly installed where  
indicated to assure an adequate  
curb to unit seal.  
Instructions for the roof curb  
assembly and installation with curb  
dimensions are provided with each  
roof curb kit.  
Figure 2 - Waterproofing  
4
3
1
2
1 = Roofcurb  
2 = Roof membrane  
3 = Seal  
4 = Rooftop  
RT-SVX19A-E4  
7
href="
Installation  
Dimensions/Weights/Clearances  
Figure 3 - Minimum clearances  
Table 2 - Minimum clearances (mm)  
Minimum clearance  
UNIT  
1
2
3
4
5
YKD/YKH 155  
YKD/YKH 175  
YKD/YKH 200  
YKD/YKH 250  
TKD/TKH 155  
TKD/TKH 175  
TKD/TKH 200  
TKD/TKH 250  
WKD/WKH 125  
WKD/WKH 155  
WKD/WKH 200  
1900  
1900  
1900  
1900  
1900  
1900  
1900  
1900  
1900  
1900  
1900  
1800  
1800  
1800  
1800  
1800  
1800  
1800  
1800  
1800  
1800  
1800  
1220  
1220  
1220  
1220  
1220  
1220  
1220  
1220  
1220  
1220  
1220  
1000  
1000  
1000  
1000  
1000  
1000  
1000  
1000  
1000  
1000  
1000  
1300  
1300  
1300  
1300  
1300  
1300  
1300  
1300  
1300  
1300  
1300  
The structure accommodating the unit(s) must be designed to support the  
equipment in operation, as a minimum. Refer toTable 3a and the space  
requirement plan.  
8
RT-SVX19A-E4  
href="
Installation  
Table 3a - Weigths & center of gravity (Figure 1)  
Maximum weight  
Corner Weight (1)  
Center of Gravity  
Shipping  
Net  
(kg)  
698  
735  
920  
946  
623  
660  
841  
866  
625  
642  
871  
A
B
C
D
Length (L)  
Width (W)  
(mm)  
737  
UNIT  
(kg)  
866  
(kg)  
243  
251  
324  
327  
219  
227  
297  
300  
218  
228  
291  
(kg)  
176  
188  
242  
251  
159  
172  
221  
230  
159  
162  
226  
(kg)  
118  
127  
151  
159  
103  
112  
138  
145  
105  
105  
155  
(kg)  
162  
169  
203  
208  
142  
149  
185  
206  
144  
147  
199  
(mm)  
1143  
1168  
1321  
1346  
1143  
1168  
1321  
1346  
1143  
1143  
1346  
YKD/YKH 155  
YKD/YKH 175  
YKD/YKH 200  
YKD/YKH 250  
TKD/TKH 155  
TKD/TKH 175  
TKD/TKH 200  
TKD/TKH 250  
WKD/WKH 125  
WKD/WKH 155  
WKD/WKH 200  
902  
737  
1128  
1154  
790  
838  
838  
711  
827  
711  
1050  
1075  
792  
838  
838  
711  
809  
711  
1080  
889  
1. Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.  
Table 3b - Weights of Options & accessories  
Motorized  
Outside Air  
Damper  
Standard Roof Adjustable Roof  
Manual Outside  
Air Damper  
UNIT  
Curb  
Curb  
220  
220  
260  
260  
Economizer  
30  
Electric heater Hot water coil  
YKD 155  
YKD 175  
YKD 200  
YKD 250  
YKH 155  
YKH 175  
YKH 200  
YKH 250  
TKD 155  
TKD 175  
TKD 200  
TKD 250  
TKH 155  
TKH 175  
TKH 200  
TKH 250  
WKD 125  
WKD 155  
WKD 200  
WKH 125  
WKH 155  
WKH 200  
93  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
27  
27  
34  
34  
27  
27  
34  
34  
27  
27  
34  
34  
27  
27  
34  
34  
27  
27  
34  
27  
27  
34  
93  
30  
107  
107  
37  
37  
30  
30  
37  
37  
93  
93  
220  
220  
260  
260  
30  
14  
14  
18  
18  
14  
14  
18  
18  
18  
18  
18  
18  
18  
18  
85  
85  
30  
107  
107  
37  
110  
110  
37  
30  
30  
37  
37  
93  
93 &nbs